ANALOG

Adjust Analog output. Switch from 4-20mA to 20-4mA
Fine tune both 4mA current and 20mA current reading
Park (Lock) Current to 4, 8 or 12mA.

• 4-20
• 20-4
• 4mA tuning
• 20mA tuning
• Park 4mA
• Park 8mA
• Park 12mA

INTERFACE(1)

Enable / Disable Interface measurement mode. See ‘Interface 
Mode’ for more information

Enable / 
Disable

FACTORY RESET

Restore all parameters to factory default.

• Yes
• No

DEVICE INFO

Display device information

 <2    

 <2 5

 <10  

 <20

 <40  

 <80

 > 80

LOCK CODE

Enable / Disable lock code. If enabled, select lock code 
number.

Enable / 
Disable

PROBECALIBR

If physical length of probe is adjusted you must run this 
routine for the system to re-detect the probe end. Nothing 
should be touching the probe when commencing this function.

• Adjustable
• Password
 protected 

(222)

PROBEFAULT

Probe Fault will activate Failsafe in the event of a missing 
Probe

Enable / 
Disable

DIST CALIBR

Calibrate distance correction factor. Some applications or
environments can affect time of flight signal travel affecting 
the measured distance reading. This function allows the 
detected distance to be adjusted to suit the application.

Adjustable

 (1)Interface mode is only available with the Interface communications option (see Part Numbers)

INTERFACE MODE SETUP

Interface mode is only avaialble with the Interface communications option (see Part Numbers).

The Interface mode is designed to measure applications with low to high dielectric constant layers.

The transmited signal relfects off the Upper Layer and continues through the Interface and reflects from the

Lower Layer.

The unit provides a level reading for both the Upper and Lower Layers available via HART. The Lower Layer

will always be transmitted to the 4-20mA output.

When Interface mode is Enabled, the following parameters are adjustable.

PARAMETER

DESCRIPTION

OPTIONS

DK COMP

Set dielectric of interface layer. This adjusts the velocity compensation for the 
transmitted signal as it passes through the interface. Default 2.22

0-100

Содержание TRACER 1000 3G LTT1-3G

Страница 1: ... 877 356 5463 p 330 331 7331 f 330 331 7172 www FLO CORP com 2018 FLO CORP REVA 0918 1 TRACER 1000 3G LTT1 3G GWR LEVEL TRANSMITTER OPERATING INSTRUCTIONS ...

Страница 2: ...l All operations described in this operating instructions manual must be carried out only by trained specialist personnel authorized by the plant operator During work on and with the device the required personal protection equipment must always be worn Warning about misuse Inappropriate or incorrect use of the instrument can give rise to application specific hazards e g vessel over fill or damage ...

Страница 3: ...emical Petrochemicals Energy Food Beverages Plastic Pellets Minerals Mining Oil Gas Pharmaceutical Pulp Paper Wastewater TECHNOLOGY The Tracer 1000 3G uses TDR Technology low energy high frequency electromagnetic impulses generated by the sensor s circuitry are propagated along the probe which is submerged in the liquid or solid to be measured When these impulses hit the surface of the media part ...

Страница 4: ...0mm Measurements per second 3 Response Time 1 second application dependant Sum of non linearity non repeatability hysteresis Analog 0 02 Repeatability 3mm Memory Non Volatile No backup battery required 10 years data retention Operating Temp Standard 40 to 176ºF 40ºC to 80ºC Optional 40 to 608ºF 40ºC to 320ºC Display 4 line graphic display 128 x 64 pixels Language English Configuration 4 button up ...

Страница 5: ...lume 2 Level Level Distance DISPLAY UNIT Adjust displayed measurement unit Centimeters Metres Feet Inches LOW LEVEL Set Low Level 4mA distance Adjustable HI LEVEL Set High Level 20mA distance Adjustable DAMPING Adjust output response time smoothness Adjustable TRACKING Program application Fill and Empty speeds Fast 90m h 265ft h Medium 30m h 98ft h Slow 10m h 32ft h InstaTrack is a special mode wh...

Страница 6: ...et value of most similar to material to be measured For Interface model type it must be the Upper Layer 4 Run Digitize routine Confirm displayed distance is either material level FAIL MODE Set Failsafe reading 3 80mA 20 20mA LastKnown 4mA 20 00mA 21 50mA FAIL TIME Set time delay for FailSafe condition in seconds Adjustable DIGITIZE The Digitize function is an automatic setup routine used to elimin...

Страница 7: ...able Disable DIST CALIBR Calibrate distance correction factor Some applications or environments can affect time of flight signal travel affecting the measured distance reading This function allows the detected distance to be adjusted to suit the application Adjustable 1 Interface mode is only available w ith the Interface communications option see Part Numbers INTERFACE MODE SETUP Interface mode i...

Страница 8: ...e application is NOT an interface application disable interface mode 2 SET HIGH AND LOW LEVEL High and Low level distances can be programmed manually or you can run Autoset Autoset can be used to program the High or Low level based on the material level which is touching the probe when the function is run 3 SET TRACKING SPEEDS Tracking speeds can be set to Fast Medium Slow and Custom measured in D...

Страница 9: ...Level 1 Level in mm Div by 304 7851 D 722 Tertiary Variable interface Height in mm Div by 304 7851 G 723 Low Level mm Div by 304 7851 724 High Level mm Div by 304 7851 725 Primary Variable Status 726 Primary Variable Level 2 Distance in mm Div by 304 7851 A 727 Primary Variable Percentage C 728 Secondary Status 729 Secondary Variable Level 1 Distance in mm Div by 304 7851 730 Secondary Variable Pe...

Страница 10: ... 877 356 5463 p 330 331 7331 f 330 331 7172 www FLO CORP com 2018 FLO CORP REVA 0918 10 Instructions for Assembling Detached Probe Handling and Mounting ...

Страница 11: ... Housing There are specific rotation points which should be used while mounting the unit into place The Housing Compartment should never be used to rotate the device during mounting For rotating the housing after installation see Rotating the Enclosure section When Installing the Tracer 3000 unit use spanner or wrench ONLY at Process Fitting as indicated ...

Страница 12: ... 877 356 5463 p 330 331 7331 f 330 331 7172 www FLO CORP com 2018 FLO CORP REVA 0918 12 Placement Requirements Nozzle Socket Mounting ...

Страница 13: ... 877 356 5463 p 330 331 7331 f 330 331 7172 www FLO CORP com 2018 FLO CORP REVA 0918 13 Stand Pipe Flanged Mounting ...

Страница 14: ...unting Non Conductive Vessel A non conductive vessel will require a conductive metal strip or equivalent connected to the metal flange or thread and running along side the vessel for at least the Probe insertion length A conductive metal sheet min 0 5m 8 should also be mounted on the roof and be in contact with metal thread or flange If a seal gasket is used between the flange and the vessel ensur...

Страница 15: ... 877 356 5463 p 330 331 7331 f 330 331 7172 www FLO CORP com 2018 FLO CORP REVA 0918 15 ...

Страница 16: ...tite 243 or equivalent on grub screws to secure once completed f Adjust ProbeCalibr Parameter in Advanced menu to represent new length password 222 Rotating Ex Rated Enclosures The Ex d gland which couples the sensing probe to the flameproof enclosure provides a critical sealing function for the enclosure Internal wires are passed through this gland and the high integrity seal This gland incorpora...

Страница 17: ...egrity seal This gland incorporates a Union Joint which is designed to rotate However this rotation is limited to one time adjustment of Display orientation after installation on site ONLY one 36mm spanner applied to the Hex of Union Joint to rotate enclosure to desired orien tation as allowed DO NOT hold the enclosure during this procedure Rotation beyond these strict limits can damage the intern...

Страница 18: ... 877 356 5463 p 330 331 7331 f 330 331 7172 www FLO CORP com 2018 FLO CORP REVA 0918 18 ...

Страница 19: ...cations For Hazardous Locations see appropriate safety instructions available at http www FLO CORP com C Check the wiring is correct and all connections are secure D Apply power to the unit When power is applied the unit will start its normal load sequence The following messages will cycle on the display When power is applied the unit will start its normal load sequence The following messages will...

Страница 20: ... 877 356 5463 p 330 331 7331 f 330 331 7172 www FLO CORP com 2018 FLO CORP REVA 0918 20 ...

Страница 21: ... 877 356 5463 p 330 331 7331 f 330 331 7172 www FLO CORP com 2018 FLO CORP REVA 0918 21 ...

Страница 22: ... 877 356 5463 p 330 331 7331 f 330 331 7172 www FLO CORP com 2018 FLO CORP REVA 0918 22 ...

Страница 23: ... 877 356 5463 p 330 331 7331 f 330 331 7172 www FLO CORP com 2018 FLO CORP REVA 0918 23 ...

Страница 24: ... 877 356 5463 p 330 331 7331 f 330 331 7172 www FLO CORP com 2018 FLO CORP REVA 0918 24 ...

Страница 25: ... 877 356 5463 p 330 331 7331 f 330 331 7172 www FLO CORP com 2018 FLO CORP REVA 0918 25 ...

Отзывы: