Installation and maintenance instructions
Control equipment
Electrical connections for Norway without transformer, (3x230 VAC)
The power unit can be used without a transformer
in Norway where 3x230 VAC is used. However, the
maximum motor load is lower for each power unit
when using 3x230 VAC; see the table on page 11.
In this case use phase L2 as a virtual neutral. Strap
between L2 and the neutral fuse on the incoming sup-
ply, see connecting on page 9, Fig. 7.
Connect the transformer as illustrated on the right.
Connect the incoming supply 3x230 V to the primary
side and the eQ (400 V) to the secondary side. Position
the transformer so that it has proper ventilation. Maxi
-
mum ambient temperature 40°C.
Primary (3*230 VAC)
Secondary (3*400 VAC +N)
Electrical connections for Norway with transformer, (3x230 VAC)
Fig. 3
Control equipment
(only for Norway)