Installation and maintenance instructions
Control equipment
Timer, push button, motion sensor and CO
2
monitor
External Timer
Push button
The timer, push button, motion sensor and CO
2
monitor
are supplied with the unit but not installed. Set the desired
function in Operational Function.
For operating control. Five set operating periods can be
selected. When necessary the maximum limitation of
operation can be achieved using jumpers in the required
position: 1, 2 or 3 hours. The operating period selected
cannot be longer than the time corresponding to the posi-
tion of the jumper. A frame for surface mounting is sup
-
plied with the unit.
NOTE!
When using an external timer do not forget to set
the internal timer in the control system to 0.
Set extended/forced operation in the handheld terminal.
The supplied frame is used for surface mounting.
Set the required operating period in the parameters below.
Type of operation Terminal block
Extended operation, low speed SU1
Forced operation, high speed SU2
MAIN INDEX UNIT OPERATING MODE
EXTERNAL CONTROL DELAY SETTING
a
a
a
MAIN INDEX UNIT OPERATING MODE
EXTERNAL CONTROL DELAY SETTING
a
a
a
SU2
SU1
Matningsspänning
(AC 230 V eller 24 V)
230 Vac
24 Vac
0 Vac
1 h
2 h
3 h
C
NC
NO
AC 230 V
AC 24 V
N
L
G
G0
SU1/SU2
1h 2h 3h 4h 5h
Matningsspänning
(AC 230 V eller 24 V)
230 Vac
24 Vac
0 Vac
1 h
2 h
3 h
C
NC
NO
AC 230 V
AC 24 V
N
L
G
G0
SU1/SU2
1h 2h 3h 4h 5h
UTGÅNG
(pulssignal)
Förlängd Forcerad
SU1 / SU2
+
-A
A3
A2
A1
LED
UTGÅNG
(pulssignal)
Förlängd Forcerad
SU1 / SU2
+
-A
A3
A2
A1
LED
Fig. 21
Fig. 22
Fig. 23
Supply voltage
(AC 230 V or 24 V)
OUTPUT
(pulse signal)
Extended/Forced
SU1 / SU2