Fläkt Woods
8666 GB 2010.06
Specifications are subject to alteration without notice
Installation and maintenance instructions
Control equipment
11
When ordering the load interrupter (STAZ-80), specify the
total power consumption.
Total current is calculated in accordance with the example
below.
Supply air fan power consumption
+ Extract air fan power consumption
+ Other power consumption approx. 1 A
= Total power consumption (bbb in STAZ-80)
Exemple:
For a 3x400 V air handling unit with a 7.5 kW
supply air fan and 4 kW extract air fan. The power
consumption for each fan can be read off from the
table above.
15,5
+ 8,8
+ 1,0
= 25,3
Total
1 motor
Output
(kW)
3x230 V 3x400 V 3x230 V 3x400 V
Current
(A)
Current
(A)
Current
(A)
Current
(A)
0,55
7,6
4
3,3
1,5
0,75
10,2
5,8
4,6
2,4
1,1
14,2
7,6
6,6
3,3
1,2
–
4,6
–
1,8
1,5
16
9,2
7,5
4,1
1,7
–
6
–
2,5
2,2
24,6
11,8
11,8
5,4
3
–
14,8
–
6,9
3,1
–
10,8
–
4,9
4
34,4
18,6
16,7
8,8
5,5
49,4
25
24,2
12
7,5
62,6
32
30,8
15,5
11
–
47
–
23
15
–
63
–
31
The size of the load interrupter depends on the total
power consumption.
Power consumption eQ
Содержание eq Controls
Страница 55: ......