Fläkt Woods
8666 GB 2010.06
Specifications are subject to alteration without notice
Installation and maintenance instructions
Control equipment
33
Connection
Ø/(BxH)
Variant 1
Output variants, kW
Variant 2
Variant 3
Minimum flow
m3/s
Ø315
3
5
9
0,12
Ø400
1
5
9
15
0,19 (0,24
1
)
Ø500
2
12
17
24
0,37
800x400
12
17
24
0,48
1100x500
17
30
43
0,82
1400x600
20
34
54
1,3
1400x800
30
48
75
1,7
Air handling unit
size
aaa
Minimum flow
m
3
/s
005
0,27
008
0,50
009
0,55
011
0,7
014
0,8
018
1,1
020
1,2
023
1,6
027
1,6
032
1,9
036
2,1
041
2,4
045
2,6
047
2,8
050
3,2
054
3,2
056
3,3
063
3,7
068
3,9
072
4,2
079
4,6
090
5,3
Minimum flows for air handling unit-mounted electric air heater, EQEK
Minimum permissible air flows for duct-mounted electric air heater, EQKK
1 Rectangular air heater (400x400) with a circular connection for output variant 3 (15kW)
2 Rectangular air heater (500x500) with circular connection, all output variants