UNIT
OPERATING FUNCTIONS
SCHEDULER PROGRAM
SCHEDULE
Set an operating sequence by weekday in the week pro
-
gram. Six switchover times can be used per weekday,
Time 1 … 6.
Parameter
Comment
Time: 1, 2, 3, 4, 5, 6
Scheduler
hh:mm
Switchover
time
Operating mode:
Ek1 Temperature setpoint economy, Fan speed low speed
Ek2 Temperature setpoint economy, Fan speed high speed
Ko1 Temperature setpoint comfort, Fan speed low speed
Ko2 Temperature setpoint comfort, Fan speed high speed
Off
Temperature setpoint off, Fan speed off
Week program
a
a
a
a
Exempel
Time 1 00:00
Off
Time 2 08:00
K02
Time 3 12:00
K01
Time 4 14:00
K02
Time 5 18:00
Off
Time 6 ** : ** Off
At 08.00 the air handling unit starts in operating mode
comfort 2, at 12.00 it switches to operating mode
comfort 1.
At 14.00 the air handling unit switches back to
comfort 2 and then shuts down at 18.00.
Where there are asterisks, e.g. *:* the scheduler is passive
and not in use.
NOTE!
Time 1 should always be 00:00 (OFF).