Fläkt Woods
8666 GB 2010.06
Specifications are subject to alteration without notice
Installation and maintenance instructions
Control equipment
35
ECONET
®
Connect Econet
®
via Modbus RTU. There are connections
in the control panel and junction box. See the Econet
®
documentation for further information.
D sub pin on
ECONET
®
Terminal block,
control panel
Function
3/2
RxD+/TxD+
5
Modbus ref
GND
8/7
Modbus –
RxD-/TxD-
NOTE!
Check the jumper for communication in the control
panel when connecting via the junction box, see page 36.
a
a
Configuration in the controller is carried out under:
MAIN INDEX CONFIGURATION CONFIGURATION 1
REF +
-
MODBUS
Fig. 36