Installation and maintenance instructions
Control equipment
a
a
a
a
a
a
Date and Time
MAIN INDEX SYSTEM OVERVIEW
Parameter
Comment
dd.mm.yyyy
Date
hh:mm:ss
Time
Logging in
START PAGE
LOGIN
Parameter COMMENT
****
The password is 2000
Holding the knob (5) down for a couple of seconds pro
-
vides a quick link to Login.
Fan setpoints
The display of actual values and setpoints is adapted
depending on the type of fan control selected.
MAIN INDEX
UNIT SETPOINTS/SETTINGS
Parameter
Value (example)
Setpoint low flow SAF
200
Setpoint high flow SAF
400
Setpoint low flow EAF
200
Setpoint high flow EAF
400
Comment: The values refer to l/s with flow control and
Pa with pressure control.
Pressure/flow alarm
Set the desired alarm limits for pressure/flow alarms.
It is possible to set both a minimum limit and maximum
limit.
MAIN INDEX
UNIT FAN CONTROL
SUPPY/EXTRACT AIR FAN SETPOINTS/SETTINGS
EXCEPTION ALARM
Temperature setpoints
a
a
a
Different menus are displayed depending on the type of
temperature control selected. There are four ways of select
-
ing how a dead zone relates to the setpoint. See below:
Parameter
Comment
H Dz
Heating setpoint with a dead zone for cooling
Heating Cooling A setpoint for both heating and cooling
Se – Dz A setpoint with half the dead zone on
either side
Cooling – Dz
Cooling setpoint with a dead zone for heating
MAIN INDEX
UNIT
TEMPERATURE CONTROL
SETPOINTS/SETTINGS
Parameter
Value Comment
(e.g. H Dz)
Setpoint comfort
21 Temperature controller comfort
setpoint
Setpoint economy 19 Temperature controller economy
setpoint
Dead zone comfort 2
Dead zone between heating and
cooling
Dead zone economy 6 Dead zone between heating and
cooling
Note: Cooling setpoint = se dead zone
Time schedules
The controller has three types of internal schedules: weekly
program, exception program and stop program. The weekly
program is programmed first with the desired daily weekday
schedule. Then the exception program and stop program are
used to enter exception periods such as weekends, holidays or
when the air handling unit should be shut down.
NOTE!
Set these for a day, time period or week day and then
specify a day program in the exception program.