eCO Side - Installation and Maintenance Manual
27
FläktGroup DC_10176GB_20180924_R3
Specifications are subject to alteration without notice
9.7 SCHEDULES, CONT.
EXAMPLE 2
Below is an example of a weekly schedule configured to run the
fans at normal speed from 08.00 to 18.00 Monday to Thursday,
from 08.00 to 17.00 on Friday and 10.00 to 14.00 on Saturday. At
all other times, the fans are turned off.
Day
Time
Fan speed
Monday
8–1 8
Normal
Tuesday
8–18
Normal
Wednesday
8–18
Normal
Thursday
8–-18
Normal
Friday
8–-17
Normal
Saturday
10–14
Normal
Other time
Stop
9. CONTROL PANEL, OPERATIONS, COMMISSIONING
EXAMPLE 3
Below is an example of a weekly schedule configured to run the
fans at normal speed from 08.00 to 18.00 Monday to Friday.
At all other times, the fans are configured to run at trickle speed.
At trickle speed the temperature set point will be decreased by
two degrees.
Day
Time
Fan speed
Temperature set point
Monday
8–18
Normal
0° C
Tuesday
8–18
Normal
0° C
Wednesday
8–18
Normal
0° C
Thursday
8–18
Normal
0° C
Friday
8–18
Normal
0° C
Other time
Trickle (Low)
–2° C
Only Weekly 1–2 should be activated.
Only Weekly 1–3 should be activated.