The unit can communicate with a Building Management System
(BMS) via Modbus (RS485 and TCP/IP). No other protocols are
supported.
11.1 MODBUS, RS485
See table below for connection of Modbus. For more information,
see the separate Modbus ins
Component
Terminal Connection
Note
Modbus, RS485
Modbus
47 – 48 – 49
REF - A - B
11.2 MODBUS, TCP/IP
The unit has a built-in Ethernet card for connection to a LAN.
Connect the Ethernet cable (RJ45) to the connector on top of the
unit.
11.3 WEBSERVER
There is a built-in webserver in the ISYteq Mini control system.
This makes it possible to read and change parameters via a
web browser.
11. COMMUNICATION
To read or change the IP-address, enter menu 8.1.