eCO Side - Installation and Maintenance Manual
38
FläktGroup DC_10176GB_20180924_R3
Specifications are subject to alteration without notice
12. PARAMETER LIST
1)
R/W = Read and write value, R = Read only value
Parameter
Type of value
1)
Range
Unit
Default value Comments
7.4 Contact function
DI1 Timer 1
R/W
NO/NC
–
NO
DI2 Timer 2
R/W
NO/NC
–
NO
DI3 RHE Rotation Guard
R/W
NO/NC
–
NO
DI4 Defrost pressure switch
R/W
NO/NC
–
NO
DI5 Filter Alarm Supply air
R/W
NO/NC
–
NO
DI6 Filter Alarm Extract air
R/W
NO/NC
–
NO
DI8 Fire Alarm
R/W
NO/NC
–
NC
DI9 Cooker Hood
R/W
NO/NC
–
NO
Not for eCO Side
DI7 Alarm Heater
R/W
NO/NC
–
NO
NC with Electrical Heater
DI10 Alarm cooling
R/W
NO/NC
–
NO
8. Configure
8.1 IP Address
R/W
Static / Dynami
–
Dynamic
Static = Manual
Dynamic = Automatic via DHCP
Subnet mask
R/W
–
–
–
Gateway
R/W
–
–
–
8.2 Menu configure
Log to USB
R/W
Yes / No
–
No
Only for troubleshooting
Unit Type
R
–
–
eCO Side
Auto logout time
R/W
0-32767
min
10
Threshold Heater
R/W
0-100
%
0
For Installers and Service Personnel
Threshold Cooling
R/W
0-100
%
0
For Installers and Service Personnel
Threshold Heat Exchanger
R/W
0-100
%
0
For Installers and Service Personnel
Threshold External Fan
R/W
0-100
%
5
For Installers and Service Personnel
8.3 Screen saver
Screensaver
R/W
On/Off
–
On
Timeout
R/W
–
min
10
8.4 Modbus BMS
Modbus Slave Address
R/W
0-255
–
2
Baudrate
R/W
9.6, 19.2, 38.4
–
19,2
Parity
R/W
None, Even, Odd
–
None
Data bits
R/W
7,8
–
8
Stop bits
R/W
1,2
–
1
8.5 Mac address
Mac address
R
–
–
–
8.6 Reset
8.6.1 Soft reset
Reset
–
–
–
–
All values are reset except adjusted air
flows and setpoints
8.6.2 Factory reset
Reset
–
–
–
–
All values are reset
8.7 Login settings
Auto Logout
R/W
Yes/No
–
Yes
Set Password 1
R/W
–
–
–
To change password
8.8 About
Software Version Control Panel
R
–
–
–
Software Version Control Board
R
–
–
–
Bootloader version Control Board
R
–
–
–