eCO Side - Installation and Maintenance Manual
35
FläktGroup DC_10176GB_20180924_R3
Specifications are subject to alteration without notice
12. PARAMETER LIST
1)
R/W = Read and write value, R = Read only value
Parameter
Type of value
1)
Range
Unit
Default value Comments
Set Date and Time
R/W
–
–
–
Set Language
R/W
–
–
Swedish
Login
R/W
0000-9999
–
0000
For installers and Service personnel
Settings
Not för eCO Side
1. Schedule
See section 9.7.
2. Commissioning Wizard
See section 9.6.
3. Timer Control
Timer control
R/W
1-6
–
1
See section 6.7
Timer Release Delay
R/W
0-9999
min
0
4. Fan Control
4.1 Fan settings
Boost Running Timer
R/W
Yes / No
–
No
Boost Running Time
R/W
0-9999
min
120
Startup Time
R/W
0-32767
s
15
Extract Fan starts directly,
Supply Fan after selected time
Shut Down Time
R/W
0-32767
s
0
180 sec for unit with Electrical heater
Fireplace
R/W
0-360
min
30
Not för eCO Side
4.2 COP / CAV
Constant pressure / Constant air volume.
For units ordered with Pressure sensors
Pressure Control Supply air
R/W
Yes/No
Yes
For unit with COP
Pressure Control Extract air
R/W
Yes/No
Yes
For unit with COP
Supply air pressure Set point
R/W
0-2000
Pa
150
Extract air pressure Set point
R/W
0-2000
Pa
150
Airflow Control Supply air
R/W
Yes/No
Yes
For unit with CAV
Airflow Control Extract air
R/W
Yes/No
Yes
For unit with CAV
Only Supply, Extract as slave
R/W
Yes/No
No
Ratio Supply/Extract
R/W
0-200
%
100
Supply, Trickle Airflow, size 04
R/W
0-9999
R/W
300
150 for size 03, 400 for size 06
Supply, Normal Airflow, size 04
R/W
0-9999
R/W
400
250 for size 03, 060 for size 06
Supply, Boost Airflow, size 04
R/W
0-9999
R/W
500
350 for size 03, 700 for size 06
Extract, Trickle Airflow, size 04
R/W
0-9999
R/W
300
150 for size 03, 400 for size 06
Extract, Normal Airflow, size 04
R/W
0-9999
R/W
400
250 for size 03, 060 for size 06
Extract, Boost Airflow, size 04
R/W
0-9999
R/W
500
350 for size 03, 700 for size 06
SETTINGS
Parameter
Type of value
1)
Range
Unit
Default value Comments
Schedules
R
–
–
–
Active schedules, read onl
y
SCHEDULES