FANS
The unit has two plug fans with EC motors.
ROTARY HEAT EXCHANGER
The speed controlled rotor is fitted with a purge sector and a ro-
tation sensor.
CONTROL SYSTEM
The ISYteq Mini control system is integrated with the unit and is
ready for use with a large number of functions.
COMPONENTS
The unit can be supplied in left-hand or right-hand configurations.
Left-hand configurations is mirror-reversed to right-hand. Refer to
the order code in Technical Instruction.
2. DESCRIPTION OF THE UNIT
FILTER
Bag filter class (F7) ePM1 50% on both supply and extract air.
POST HEATER, HOT WATER
Hot water coil containing copper tubes and aluminum fins. Pipe
connection ø15 mm. Freeze protection temperature sensor is
included. Max operating pressure
3.0
MPa.
POST HEATER, ELECTRICAL
The heater for size 03 and 04 is built-in. For size 06 the heater is
duct mounted.
TOP RIGHT HAND CONFIGURATION RDSP, bb = 12 or 14
BOTTOM RIGHT-HAND CONFIGURATION RDSP, bb = 11 or 13
EXHAUST AIR UPWARDS RDSP, bb = 11 or 13 and c = 2
1 Outdoor air sensor GT3
2 Supply filter
3 Rotary heat exchanger with rotation sensor
4 Supply fan
5 Electrical heater including overheating
protection alternativelyhot water coil
with freeze protection GT5
6 Supply air sensor GT1
7 Extract air sensor GT12
8 Control equipment
9 Extract filter
10 Exhaust fan
11 Pressure guard
Outdoor air
Supply air
Extract air
Exhaust air
3
4
5
6
1
2
10
11
8
7
9
6
4
8
5
3
7
9
10
1
2
11