5.3.4 Protection conductor:
The standard Panda generator is grounded. The 3-phase connection (delta) centre point is bridged to earth in the
AC output terminal box (mounted on the generator). This is the initial earth safety point and is sufficient to ensure
safe operation however only as long as no other system is installed. This system is adapted to enable test running of
the generator before delivery.
The bridge to ground (PEN) is only effective when all components in the electrical system share a common ground.
The bridge to ground can be removed and reconnected to another ground system if required for other safety stand-
ards.
Full voltage connections are mounted in the electrical cabinet. It must be ensured that the electrical cabinet is
secured and closed while the generator is running.
The starter battery cable should be disconnected when work is being done on either the generator or the electrical
system in order to prevent accidental starting of the generator.
5.3.5 Operating control system on the Fischer Panda generator
Fischer Panda generators are equipped with various sensors/temperatures switches. The combustion engine is fur-
ther equipped with a oil pressure control switch, which switches the motor off, if the oil pressure sinks to a particular
level.
5.4
Instructions for capacitors - not present at all models
CAUTION!
Danger to Life - High voltage
Do not touch the capacitor contact terminals!
The generator's electrical system requires two different groups of capacitors:
A) The booster capacitors
B) The operating capacitors
Both types are mounted in the electrical cabinet. (At some models direct on the generator)
Capacitors store an electrical charge. It is possible that even after they have been disconnected stored energy is still
held. Therefore it is essential that the connectors are not touched.
Should it be necessary to check or test the capacitors, they should be shorted out by using an insulated screw driver.
The operating capacitors are automatically discharged when the generator is stopped in the normal way. The
booster capacitors will be discharged through internal resistors.
For safety however, the capacitors have to be discharged (short circuited) prior to carrying out any work on the AC-
Control box.
5.5
Checks before start - see remote control panel data sheet
Note:
The instructions and regulations of the remote control
panel data sheet must be respected.
Respect the safety instruction in front of this manual.
Содержание 45i pms
Страница 3: ...8 10 14 Kapitel Chapter A Seite Page 3...
Страница 4: ...Seite Page 4 Kaptitel Chapter A 8 10 14...
Страница 12: ...Seite Page 12 Kaptitel Chapter 1 8 10 14...
Страница 148: ...Generator Failure Seite Page 148 Kaptitel Chapter 8 Generator Failure 8 10 14...
Страница 160: ...Tables Seite Page 160 Kaptitel Chapter 9 Tables 8 10 14...
Страница 176: ...Inverter Panda PMGi 45 Seite Page 176 Kaptitel Chapter 10 Inverter Panda PMGi 45 8 10 14...
Страница 204: ...Seite Page 204 Kapitel Chapter 3 Installation 8 10 14 Leere Seite Intentionally blank Installation...
Страница 206: ...Seite Page 206 Kapitel Chapter 4 Maintenance 8 10 14 Leere Seite Intentionally blank Maintenance...
Страница 212: ...Seite Page 212 Kapitel Chapter 6 Annex 8 10 14 Leere Seite Intentionally blank Annex...