Kapitel/Chapter 10: Inverter Panda PMGi 45 - Seite/Page 165
Fischer Panda Datenblatt / Datasheet
10.4 Settings for the use of iGenerators with power inverter
ATTENTION: Wrong settings can destroy the
PMGi
For the use of power inverter with the PMGi, the settings of the power
inverter must be modified.
Wrong settings can damage or destroy the PMGi.
The settings for the Victron power inverter must be adapted for the power inverters of other brands.
10.4.1 Settings in the Victron VE Configure II Software - General
Fig. 10.4.1-1: Settings in the Victron VE configure II Software
10.4.1.1 Uninterrupted AC power (UPS function)
Due to the fact that the power inverter connects the shore power immediately to the domestic grid (to fast), the PMGi
gets overloaded and shut down with an error.
UPS Function must be deactivated.
10.4.1.2 Dynamic current limiter
With inductive load the dynamic current limiter will raise up the Voltage in the DC circuit. These over voltage can
damage or destroy the PMGi.
Dynamic current limiter must be deactivated.
Содержание 45i pms
Страница 3: ...8 10 14 Kapitel Chapter A Seite Page 3...
Страница 4: ...Seite Page 4 Kaptitel Chapter A 8 10 14...
Страница 12: ...Seite Page 12 Kaptitel Chapter 1 8 10 14...
Страница 148: ...Generator Failure Seite Page 148 Kaptitel Chapter 8 Generator Failure 8 10 14...
Страница 160: ...Tables Seite Page 160 Kaptitel Chapter 9 Tables 8 10 14...
Страница 176: ...Inverter Panda PMGi 45 Seite Page 176 Kaptitel Chapter 10 Inverter Panda PMGi 45 8 10 14...
Страница 204: ...Seite Page 204 Kapitel Chapter 3 Installation 8 10 14 Leere Seite Intentionally blank Installation...
Страница 206: ...Seite Page 206 Kapitel Chapter 4 Maintenance 8 10 14 Leere Seite Intentionally blank Maintenance...
Страница 212: ...Seite Page 212 Kapitel Chapter 6 Annex 8 10 14 Leere Seite Intentionally blank Annex...