![Fischer Panda 45i pms Скачать руководство пользователя страница 125](http://html1.mh-extra.com/html/fischer-panda/45i-pms/45i-pms_user-manual_2294277125.webp)
Maintenance Instructions
8.10.14
Kapitel/Chapter 7: Maintenance Instructions - Seite/Page 125
Fig. 7.16-5: Injection nozzles
Removing the nozzle heat shield ring seal within the scope of
the maintenance work.
IMPORTANT!
• Use a phillips screwdriver (1) with a diameter greater than
the hole in the heat ring seal (approx. 6 mm (1/4 in)).
1. Lightly turn the screwdriver (1) into the hole in the heat
ring seal.
2. Rotate the screwdriver three to four times in each direc-
tion.
3. When rotating the screwdriver, slowly extract the heat ring
seal (4) together with the injection nozzle gasket (3).
4. If the heat ring seal drops back in, repeat the procedure
above.
For assembly:
• If the injection nozzle is uninstalled for cleaning or maintenance purposes, the heat seal ring and the injection nozzle
gasket must be replaced.
(1) Phillips screwdriver (2) Injection nozzle
(3) Injection nozzle gasket (4) Heat ring seal
Содержание 45i pms
Страница 3: ...8 10 14 Kapitel Chapter A Seite Page 3...
Страница 4: ...Seite Page 4 Kaptitel Chapter A 8 10 14...
Страница 12: ...Seite Page 12 Kaptitel Chapter 1 8 10 14...
Страница 148: ...Generator Failure Seite Page 148 Kaptitel Chapter 8 Generator Failure 8 10 14...
Страница 160: ...Tables Seite Page 160 Kaptitel Chapter 9 Tables 8 10 14...
Страница 176: ...Inverter Panda PMGi 45 Seite Page 176 Kaptitel Chapter 10 Inverter Panda PMGi 45 8 10 14...
Страница 204: ...Seite Page 204 Kapitel Chapter 3 Installation 8 10 14 Leere Seite Intentionally blank Installation...
Страница 206: ...Seite Page 206 Kapitel Chapter 4 Maintenance 8 10 14 Leere Seite Intentionally blank Maintenance...
Страница 212: ...Seite Page 212 Kapitel Chapter 6 Annex 8 10 14 Leere Seite Intentionally blank Annex...