16.9 Installation of the PMGi
The PMGi must be mounted vertical, with the electrical connection down. So you can read the writing on the PMGi.
The surface where the PMGi is mounted should be smoothed and support the heat transfer. The Air holes and Air
grille must be not covered and enough cooling air must be pleasant at any time for the PMGi.
To mount the PMGi use the four fixing holes diameter 6,5mm.
Note!
See the safety instruction in your Generator and iControl
Manual.
The rules of the respective regional authority must be adhered to. Only an electrician may carry out installation of the
electrical connections for safety reasons.
16.9.1 Electrical connection.
Only special trained persons are allowed to make the electrical connection.
When an extension cable is required, be sure to use a though rubber heated flexible and fireproof cable. Limit length
of extension cables depends on the voltage drop along the cable. This drop must be less than 2,5% value of the
nominal output voltage.
Pay attention to the right pin assignment. See “Socket pins of the PMGi 8000” on page 206.
16.9.1.1 Connection to a system with RCD
The PMGi is prepared for the use in a RCD protected grid.,
The PMGi out must be connected 1:1 (PE,N,L) to the customers electrical cabinet. The Life wire and neutral wire will
be connected to the RCD. The PE will be connected to the PE of the electrical cabinet. After installation the function
of the RCD must be tested.
Fig. 16.9-1: PE-N bridge
PE-N Bridge
Inside of the PMGi a PE-N bridge
16.9.1.2 Connection to a system with isolation control
For the use of the PMGi with an isolation controlled grid, the internal PWE-N Bridge must be disconnected.
A Manual for this modification can be downloaded under:
http://www.fischerpanda.de/images/gensets/M_AC_50_INV_PMS_8000i/operatormanual/PMGi/
Modification_PMGi_isolation_control.eng.pdf
1
Содержание 10000i
Страница 10: ...Seite Page 10 Kapitel Chapter 2 16 1 15 Leere Seite Intentionally blank ...
Страница 146: ...Maintenance Instructions Seite Page 146 Kaptitel Chapter 7 Maintenance Instructions 16 1 15 7 22 ...
Страница 156: ...Generator Failure Seite Page 156 Kaptitel Chapter 8 Generator Failure 16 1 15 ...
Страница 194: ...Seite Page 194 Kapitel Chapter 12 Installation 16 1 15 Leere Seite Intentionally blank Installation ...
Страница 196: ...Seite Page 196 Kapitel Chapter 13 Maintenance 16 1 15 Leere Seite Intentionally blank Maintenance ...
Страница 202: ...Seite Page 202 Kapitel Chapter 15 Annex 16 1 15 Leere Seite Intentionally blank Annex ...