8. FLOOR PROTECTOR REQUIREMENTS FOR A NON-
MASONRY BUILT-IN CANOPY WITH HEAT SENSITIVE FLOOR
An
Insulated
Floor
Protector (Hearth) must
consist of a minimum of
20mm
of Insulation
board (Micore 160,
Supalux, Promatech H,
Eterpan LD or product of
similar thermal
resistance) and tiles/slate
or similar with sealed
joints on top surface to
protect from spilt
ash/embers.
Dimensions A & B from above diagram must meet the following schedule:
B HEIGHT (mm) A FROM FIRE BREAST
40mm
500mm
Minimum width of floor protector must be 840mm and/or 420mm from centre of
heater.
HEAT SENSITIVE FLOOR
INSULATED FLOOR PROTECTOR
WALL
A
FASCIA
B
SUPERLUX
BUILT-IN CANOPY BOX INSULATION
BUILT IN CANOPY BOX
Diagram 17
Содержание kompact ag
Страница 13: ...Kompact RU Installation Version 14 4 14 13 Diagram 9 ...
Страница 16: ...Kompact RU Installation Version 14 4 14 16 Diagram 12 ...
Страница 19: ...Kompact RU Installation Version 14 4 14 19 Diagram 15 ...
Страница 29: ...Kompact RU Installation Version 14 4 14 29 KOMPACT WITH ATHENA FASCIA ...
Страница 31: ...Kompact RU Installation Version 14 4 14 31 KOMPACT WITH DECO FASCIA ...
Страница 33: ...Kompact RU Installation Version 14 4 14 33 KOMPACT WITH FORTE FASCIA ...
Страница 35: ...Kompact RU Installation Version 14 4 14 35 KOMPACT WITH 760MM PLAZA FASCIA 760mm Fascia Masonry ONLY 780 ...
Страница 38: ...Kompact RU Installation Version 14 4 14 38 KOMPACT WITH SERENITY 4 SIDED FASCIA ...