Notifier Inertia-888 User, Technical & Programming Manual
Copyright (c) 2005, Notifier Inertia
INSTRUCTIONS TO OPERATORS
CONTROLS AND INDICATORS
INDICATIONS
INDICATOR
ON WHEN:
MAINS ON
Panel is running on mains supply
BATTERY FAULT
Battery fails test or has been disconnected. Fault will remain on until a
battery test passes.
PSU FAULT
Battery Charger > 28.2 or < 26.4
Panel Supply > 28.2 or < 21
ACF ACTIVATED
ACF Output Is Operated
ACF ISOLATED
ACF Output Is Isolated
ACF FAULT
ACF Output Is Open Circuit or Short Circuit
EXT BELL ISOLATE
Bell Output Is Isolated
EXT BELL FAULT
Bell Output Is Open Circuit or Short Circuit
WARN SYS
ISOLATED
Warning System Output Is Isolated
WARN SYS FAULT
(LD8 on
Termination Board)
Warning System Output Is Open Circuit or Short Circuit
AZF ALM 1-8
Flashes When Zone Is In Alarm
Steady When Zone Is In Pre-Alarm
Steady When Zone Is In Alarm But Isolated or Acknowledged
AZF FLT 1-8
Zone Is In Fault
AZF ISO 1-8
Zone Is Isolated
KEYPAD CONTROLS
BUTTON
FUNCTION
ACF ISOLATE
Toggles ACF Isolate On/Off (Also used in Programming Mode)
ACF RESET
Resets The ACF If Latched On
BATTERY TEST
Initiates A Battery Test For 60 Seconds
AUTO TEST
Initiates An Auto Test Of System Functions
WALK TEST
Initiates Detector "Walk Test" Mode On Panel
PROGRAM
Used For Programming Mode, Refer Programming Section
AUX RELAY
Used For Programming Mode, Refer Programming Section
ALARM TEST
Alarm Test (Zone), Followed By Zone Number
FAULT TEST
Fault Test (Zone), Followed By Zone Number
ISOLATE
Isolate (Zone) , Followed By Zone Number
RESET
Reset (Zone), Followed By Zone Number
ALL AZF
Substitutes For A Zone Number As "All Zones"
1,2,3,4,5,6,7,8
Zone Numbers.