Notifier Inertia-888 User, Technical & Programming Manual
Copyright (c) 2005, Notifier Inertia
BATTERY TEST
BATTERY
TEST
This function tests the performance of the batteries fitted to the system. Pressing this
button will initiate a battery test as specified in AS1603.4. The test will temporarily
disconnect the batteries from the panel and apply load on the batteries for 60 seconds. The
pressing of any key during the test period will abort the battery test and return the system
back to normal mode.
If the test fails, the "Battery Fault" indicator will turn on and the buzzer will sound
continuously, only a successful battery test will turn the indicator off.
WALK TEST MODE
WALK
TEST
This function will place the panel into "walk test" mode. Walk test mode is used for the on-
site testing of detector zones. This mode cannot be selected if any zone(s) is in alarm.
Entry to walk test mode will be acknowledged by three beeps and the isolate LED's will
flash on all zones.
If the bells are not required to ring during walk test, simply press the "BELL ISOLATE" key
once. The bell isolate LED will illuminate to verify that the bells have been isolated.
Any alarm signal from detectors etc. will be received by the panel on its appropriate zone.
The panel will beep to acknowledge receipt of the alarm and indicate the alarm by
illuminating the appropriate alarm LED for 4 seconds (the bells will also ring for a 1 second
period unless previously isolated).
The zone and detector will then be automatically reset.
Pressing any key will terminate the walk test mode and return the panel back to normal
operation, restoring all zone types and output configurations also ensuring that bell and
ancillary outputs are de-isolated. The bells will give three pulses of 1 second each to warn
any testers still in the building that walk test mode has been terminated.
Failure to receive any alarms or keystrokes within a 15 minutes period will result in the
panel automatically exiting walk test mode and returning back to normal as follows;
Bell outputs to be de-isolated.
Ancillary outputs to be de-isolated.
Bell will sound 3 times, each of 1 second duration.
Exit from walk test mode.
Zone types and output configurations restored