Page
7
Notifier Inertia-888 User, Technical & Programming Manual
Copyright (c) 2005, Notifier Inertia
OUTPUTS
Name
Description
Type
Function
SBY
Standby
Normall Energised -
Clean Contact
Changes when panel
supply drops below 21V
AUX
Auxiliary
Contact
Clean Contacts
Programmable
FLT
Fault Output
Normall Energised -
Clean Contact
Activates on any Fault
GEN
General Alarm
Clean Contact
Activates on any Alarm
WARN
Warning
System
Output
Monitored - Powered
Activates on any Alarm
24V (nom) 0.5A
BELL
Bell Output
Monitored - Powered
Activates on any Alarm
24V (nom) 0.5A
ACF
Ancillary
Control
Output
Monitored - Powered
Activates on any Alarm
24V (nom) 0.5A
AUX
Power
Power Output
24V (nom) 0.5A Max
Used to Power Auxiliary
Loads up to 0.5A Total
Contact Ratings: 24V DC (nom) 0.5A