Master Programming Level
Programming
MS-5UD and MS-10UD Series Manual —
P/N 52626:B1 6/30/2009
91
Enter the digits as you would like the number to be dialed. For example, if it’s necessary to dial
9 before dialing a number outside the building, you may wish to pause after dialing 9. Enter
9
followed by
D
for a three second pause or
E
for a five second pause then the phone number
followed by an F to indicate the end of the number.
Communication Format
Pressing
1
while viewing Primary/Secondary Screen #3 will cause the following screen to be
displayed:
The Communication Format is determined by the type of receiver that the DACT is transmitting
to.
Consult your Central Station for proper selection or consult our factory representatives.
For any format chosen, the control panel automatically programs all of the event codes.
Select the Communication Format by pressing the corresponding number key while viewing the
Comm Format screen. The following table describes each format:
Event Codes
Pressing
2
while viewing Primary/Secondary Screen #3 will cause the following screen to be
displayed:
Pressing the down arrow key allows viewing of all Events associated with the selected
Communication Format. Pressing the number corresponding to the event displayed in each
screen will display its default active and restoral event codes which can be customized by the
programmer.
For example, if Ademco Contact ID is the selected format, pressing
3
for Zone 3 Alarm will
display the following screen which allows the Event Code to be changed from the default value.
Table 3.1 Communication Formats
Screen Selection
Communication Format Description
ADEMCO CONTACT ID
Contact ID, DTMF, 1400/2300 ACK
SIA-DCS-8
Security Industry Association, 8 messages per call
SIA-DCS-20
Security Industry Association, 20 messages per call
CENTRAL STATION
1=COMM FORMAT
2=EVENT CODES
Primary/Secondary Screen #3
COMM FORMAT
1=ADEMCO CONTACT ID
2=SIA-DCS-8
3=SIA-DCS-20
EVENT CODES
1=ZONE 1 ALARM
2=ZONE 2 ALARM
3=ZONE 3 ALARM
Event Code Screen
ZONE 3 ACTIVE
115
Содержание MS-10UD Series
Страница 54: ...Installation ANN BUS Audio Panel 54 MS 5UD and MS 10UD Series Manual P N 52626 B1 6 30 2009 Notes ...
Страница 108: ...Programming Maintenance Programming Level 108 MS 5UD and MS 10UD Series Manual P N 52626 B1 6 30 2009 Notes ...
Страница 158: ...158 MS 5UD and MS 10UD Series Manual P N 52626 B1 6 30 2009 Z Z Index ...
Страница 160: ...World Headquarters 1 Firelite Place Northford CT 06472 1653 USA 203 484 7161 fax 203 484 7118 www firelite com ...