Operating Instructions
Process Monitor Operation
114
MS-5UD and MS-10UD Series Manual —
P/N 52626:B1 6/30/2009
4.7 Process Monitor Operation
Process Monitor operation will initiate the following events:
•
The piezo sounder pulses ¼ second On and ¼ second Off
•
The LCD displays a process monitor message along with the device name, type, adjective/
noun, associated zones and time/date
•
Communicate the process monitor condition to the Central Station
•
Relays programmed for process monitoring will be activated
•
The alarm relay is not activated
•
Silenced alarms are not resounded
•
Timers are not started
•
Store event in history buffer
Note that, like supervisories, process monitor signals latch, except when programmed for process
monitor autoresettable.
4.8 Hazard/Tornado Condition Operation
Hazard/Tornado Condition operation will initiate the following events:
•
The piezo sounder pulses ½ second On, ½ second Off
•
The LCD displays a hazard message along with the device name, type, adjective/noun,
associated zones and time/date
•
Communicate the hazard condition to the Central Station
•
Relays programmed for hazard will be activated
•
The alarm relay is not activated
•
Silenced alarms are not resounded
•
Timers are not started
•
Store event in history buffer
•
Supervisory LED flashes ½ second On, ½ second Off
Hazard conditions latch.
4.9 Medical Alert Condition Operation
Medical Alert Condition operation will initiate the following events:
•
The piezo sounder ½ second On, ½ second Off
•
The LCD displays a medical alert message along with the device name, type, adjective/noun,
associated zones and time/date
•
Communicate the medical alert condition to the Central Station
•
Relays programmed for medical alert will be activated
•
The alarm relay is not activated
•
Silenced alarms are not resounded
•
Timers are not started
•
Store event in history buffer
•
Supervisory LED flashes ½ second On, ½ second Off
Medical alert conditions latch.
Содержание MS-10UD Series
Страница 54: ...Installation ANN BUS Audio Panel 54 MS 5UD and MS 10UD Series Manual P N 52626 B1 6 30 2009 Notes ...
Страница 108: ...Programming Maintenance Programming Level 108 MS 5UD and MS 10UD Series Manual P N 52626 B1 6 30 2009 Notes ...
Страница 158: ...158 MS 5UD and MS 10UD Series Manual P N 52626 B1 6 30 2009 Z Z Index ...
Страница 160: ...World Headquarters 1 Firelite Place Northford CT 06472 1653 USA 203 484 7161 fax 203 484 7118 www firelite com ...