Master Programming Level
Programming
MS-5UD and MS-10UD Series Manual —
P/N 52626:B1 6/30/2009
73
3.5.4 System Setup
System Setup allows the programmer to configure the following control panel features:
•
Timers:
This option allows the programmer to set the PAS (Positive Alarm Sequence) time
delay, Pre-Signal time delay and Waterflow time delay
•
Banner:
This option allows the user to change the top two lines of the LCD display from the
factory default readout, which is blank, to a user defined readout when the control panel is in
Normal condition
•
Time-Date:
This feature allows the programmer to set the time, display format (24 hr or 12
hr), date and daylight savings time feature into the FACP memory
•
Trouble Reminder
: This feature, when enabled, provides an audible reminder that an alarm or
trouble still exists on the FACP after the control panel has been silenced. The control panel
piezo sounder will pulse once every 15 seconds during an alarm and every two minutes
during a trouble condition, after the Alarm Silence or Acknowledge key is pressed. The
piezo will continue to sound at these rates until the alarm or trouble condition is cleared. If
the
Trouble Reminder
feature is not enabled and a trouble condition is not cleared within 24
hours, the panel will reactivate the trouble sounder and retransmit the trouble condition to the
central station if connected
•
Canadian Option:
This option allows the automatic programming of the FACP to Canadian
specifications (refer to "Canadian Option" on page 79).
Important! For Canadian Applications, this option must be set to ON prior to any other
panel programming.
•
Charger Disable:
This option allows the programmer to disable the onboard battery charger
in the event an external battery charger is being used
Pressing
1
for System Setup, while viewing Programming Screen #2, will cause the following
screens to be displayed:
PROGRAMMING
1=SYSTEM SETUP
2=OPTION MODULES
3=HISTORY
Programming Screen #2
SYSTEM SETUP
1=TIMERS
2=BANNER
3=TIME-DATE
System Setup Screen #1
SYSTEM SETUP
1=TROUBLE REMIND NO
2=CANADIAN OPTION OFF
3=CHARGR DISABLE NO
System Setup Screen #2
Содержание MS-10UD Series
Страница 54: ...Installation ANN BUS Audio Panel 54 MS 5UD and MS 10UD Series Manual P N 52626 B1 6 30 2009 Notes ...
Страница 108: ...Programming Maintenance Programming Level 108 MS 5UD and MS 10UD Series Manual P N 52626 B1 6 30 2009 Notes ...
Страница 158: ...158 MS 5UD and MS 10UD Series Manual P N 52626 B1 6 30 2009 Z Z Index ...
Страница 160: ...World Headquarters 1 Firelite Place Northford CT 06472 1653 USA 203 484 7161 fax 203 484 7118 www firelite com ...