Programming
Initial Power-up
56
MS-5UD and MS-10UD Series Manual —
P/N 52626:B1 6/30/2009
Pressing
1
, while this screen is being displayed, will cause the control panel to enter the Read
Status Mode which allows the user to view the programmed features and status of the control panel
The Read Status feature is not password protected. Refer to "Read Status" on page 119 for a
detailed description of this feature.
Pressing
2
will select user Programming Mode which may only be accomplished by an authorized
person. After pressing
2
, a screen will prompt for a password. After entering the correct password,
the user may select from a list of programming options.
Pressing
4
will select Remote Download which allows the user to enable the remote programming
option. Refer to "Remote Download" on page 130.
Exit Programming and Read Status Mode
The programmer can exit any mode by repeatedly pressing the keypad
ESC
(Escape) key until the
display reads System All Normal. Ten minutes of inactivity will also cause the panel to exit
Programming Mode
Note that the data which is entered during Programming mode is not saved
until the programmer exits this mode by repeatedly pressing the ‘ESC’ key. If the Reset key is
pressed or power is lost before exiting Programming mode, all data just entered will be lost
.
User Programming Levels
There are two user programming levels:
•
User Master Program Level 1 is used for programming panel specific data relating to device
types, zoning, messages, control panel functions, etc.
•
User Maintenance Program Level 2 is used by a qualified operator to access features such as
Disable/Enable, View and Clear History, Walktest and System Time Change.
3.2 Initial Power-up
The following sections describe the initial programming procedures for a new system. The same
procedures are used to modify programming in an existing system.
After completing the wiring of devices to the FACP, apply power to the control panel. If wiring has
not been completed and/or End-of-Line resistors are not installed at the panel, a trouble condition
will be indicated at the panel and a trouble message will be displayed on the LCD. Following is an
example of a possible trouble message that may be displayed.
3.3 Programming Screens Description
Three options are available when the
Enter
key is pressed: Read Status, Programming and Remote
Download Mode. The Read Status and Programming options have multiple functions or features
which may be chosen. To view all of the choices, it is necessary that the programmer scroll through
a number of additional
subscreens
. These selections are displayed on multiple screens to make
them more readable for the programmer. Refer to "Master Programming Level" on page 58, for
additional information on the various screens.
The title of the main option screen will always be displayed at the top of the subscreens for the
programmer’s convenience. If additional subscreens exist, an Up or Down arrow will be displayed
in the upper right corner of the screen being viewed. The programmer can then press the keypad
Up or Down arrow key to view the new subscreen. To select one of the choices in a screen, the
programmer presses the keypad numerical key corresponding to the desired choice.
Note that subscreens may also have multiple options which require viewing more than one screen.
The same process, as detailed in the previous paragraphs, is followed to view all option choices.
See Page
TROUBL PULL STATION
ZONE 1 OPEN FAULT
09:03A 070707
See Page
Содержание MS-10UD Series
Страница 54: ...Installation ANN BUS Audio Panel 54 MS 5UD and MS 10UD Series Manual P N 52626 B1 6 30 2009 Notes ...
Страница 108: ...Programming Maintenance Programming Level 108 MS 5UD and MS 10UD Series Manual P N 52626 B1 6 30 2009 Notes ...
Страница 158: ...158 MS 5UD and MS 10UD Series Manual P N 52626 B1 6 30 2009 Z Z Index ...
Страница 160: ...World Headquarters 1 Firelite Place Northford CT 06472 1653 USA 203 484 7161 fax 203 484 7118 www firelite com ...