Master Programming Level
Programming
MS-5UD and MS-10UD Series Manual —
P/N 52626:B1 6/30/2009
71
3.5.2.4 Auto Silence
The Auto Silence feature, when enabled, automatically silences all main circuit board
silenceable notification appliances after a programmed length of time. To enable this feature
and program the time delay before Auto Silence activation, press
2
while viewing NAC Screen
#2. The following screens will be displayed:
To disable the Auto Silence feature, press
1
for
No
while viewing Auto Silence Screen #1. To
enable the Auto Silence feature, press the number corresponding to the time delay which will
elapse before Auto Silence activates. This information will be stored in memory and the
display will return to NAC Screen #1.
3.5.2.5 Silence Inhibited
The Silence Inhibit feature, when enabled, prevents the silencing of the selected main circuit
board NAC for a period of one minute. Resetting the FACP will also be prevented for one
minute while the NAC programmed for silence inhibit is activated. Pressing
3
while viewing
NAC Screen #2 will cause the display to change from the factory default of
Silence Inhibit No
to
Silence Inhibit Yes
. Each press of the
3
key will cause the display to toggle between the two
options.
3.5.3 Relays
Pressing
3
while viewing Programming Screen #1 will allow the programmer to configure the three
main circuit board Form-C relays. The following screen will be displayed:
PROGRAM NAC #
1=SILENCEABLE YES
2=AUTO SILENCE NO
3=SIL INHIBITED NO
NAC Screen #2
AUTO SILENCE
1=NO
2=5 MINUTES
3=10 MINUTES
Auto Silence Screen #1
AUTO SILENCE
1=30 MINUTES
Auto Silence Screen #2
AUTO SILENCE
1=15 MINUTES
2=20 MINUTES
3=25 MINUTES
Auto Silence Screen #3
PROGRAMMING
1=INPUT ZONES
2=NACS
3=RELAYS
Programming Screen #1
RELAYS
1=RELAY 1 ALARM
2=RELAY 2 TROUBLE
3=RELAY 3 SUPERV
Relays Selection Screen
Содержание MS-10UD Series
Страница 54: ...Installation ANN BUS Audio Panel 54 MS 5UD and MS 10UD Series Manual P N 52626 B1 6 30 2009 Notes ...
Страница 108: ...Programming Maintenance Programming Level 108 MS 5UD and MS 10UD Series Manual P N 52626 B1 6 30 2009 Notes ...
Страница 158: ...158 MS 5UD and MS 10UD Series Manual P N 52626 B1 6 30 2009 Z Z Index ...
Страница 160: ...World Headquarters 1 Firelite Place Northford CT 06472 1653 USA 203 484 7161 fax 203 484 7118 www firelite com ...