Programming
Master Programming Level
90
MS-5UD and MS-10UD Series Manual —
P/N 52626:B1 6/30/2009
Account Code
Pressing
2
while viewing Primary/Secondary Screen #1 will cause the following screen to be
displayed:
The Account Code, which is assigned by a Central Station, depends on the communication
format being used. The Account Code screen will have a flashing cursor in the lower left
corner. Program the supplied 4-digit account code using 0 - 9 and A - F keys. Enter the first
digit, then press the right arrow key to move the cursor to the right, one position. Repeat the
process until all digits are entered.
24 Hour Test Time
Pressing 3 while viewing Primary/Secondary Screen #1 will cause the following screen to be
displayed:
Use the 24 Hour Test Time screen to program the time that the DACT will transmit the 24 Hour
Test to the Central Station. A flashing cursor will appear in the lower left corner of the screen.
Enter a four digit number representing the test time using military time (0000 = midnight and
2359 = 11:59PM).
Phone Number
Pressing
1
while viewing Primary/Secondary Screen #2 will cause the following screen to be
displayed:
The Phone Number screen is used to enter the Central Station phone number that the DACT
will be contacting. A maximum of 20 characters can be entered with valid entries being 0 - 9
and A - C where A = *, B = # and C = look for secondary dial tone for up to 2 seconds (then dial
anyway).
A flashing cursor will appear in the lower left corner of the screen. Enter the first digit then
press the right arrow key to move the cursor to the right one position. Enter the second digit
and repeat the process until all digits are entered. Press the
Enter
key to store the phone number
in memory.
ACCOUNT CODE
RANGE 0000-FFFF
Account Codes Screen
CENTRAL STATION
1=TEST TIME INT
2=ACCOUNT CODE
3=24HR T TIME
Primary/Secondary Screen #1
24 HOUR TEST TIME
ENTR USING 24HR TIME
RANGE 0000-2359
24 Hour Test Time Screen
CENTRAL STATION
1=PHONE NUMBER
Primary/Secondary Screen #2
PHONE NUMBER
20 NUMBERS MAXIMUM
Phone Number Screen
Содержание MS-10UD Series
Страница 54: ...Installation ANN BUS Audio Panel 54 MS 5UD and MS 10UD Series Manual P N 52626 B1 6 30 2009 Notes ...
Страница 108: ...Programming Maintenance Programming Level 108 MS 5UD and MS 10UD Series Manual P N 52626 B1 6 30 2009 Notes ...
Страница 158: ...158 MS 5UD and MS 10UD Series Manual P N 52626 B1 6 30 2009 Z Z Index ...
Страница 160: ...World Headquarters 1 Firelite Place Northford CT 06472 1653 USA 203 484 7161 fax 203 484 7118 www firelite com ...