130
SECTION 6
Local/Remote Site Upload/Download
The control panel may be programmed or interrogated off-site via the public switched telephone
network or locally using a USB cable. Any personal computer with Windows
™
XP or later, with a
2400 baud compatible modem or USB port and Upload/Download software PS-Tools on the CD
ROM P/N PK-CD, may serve as a Service Terminal. This allows download of the entire program
or upload of the entire program, history file, walktest data, current status, system voltages, time and
date.
Upload/Download Preparation
The PK-CD must be placed into the personal computer CD drive and the instructions that come
with it must be followed to install the PS-Tools utility onto the computer. Once the is done, the PS-
Tools utility must be set up to communicate using either a USB serial port or a dial-up modem.
For local USB programming, a standard
male-A to male-B
USB cable must be connected from the
PC’s USB port to the fire panel’s USB port (J11).
For remote modem programming, you must have the fire panel’s primary line telephone number
entered in the PS-Tools site information screens for that site. You must also change the fire panel’s
ring count from zero (the default) to answer after at least one ring.
Important: Modification of FACP programming requires that the panel be enabled for download
(refer to "Remote Download" on page 130). Remote interrogation of panel programming, history
logs, detector status, etc., is possible without enabling the remote download option.
CAUTION
: After successfully downloading a program, make certain to perform the following
steps:
1. Print out all programmed data via Print Mode or manually view programmed entries and
compare to intended program data
2. Test all affected panel operations
3. Immediately correct any problems found
6.1 Remote Download
NFPA 72 requirements state that a technician must be on-site and at the control panel whenever the
Programming Utility is used to download any information to the FACP. This applies to local and
remote programming. For this reason, a new option has been added to the FACP which allows an
individual at the FACP to enter a password and either enable the proprietary mode where
downloading will be allowed at any time or access a specific password protected screen where
downloading will be allowed regardless of the current proprietary setting. The Remote Download
option can be selected from the main menu screen as shown below:
1=READ STATUS MODE
2=PROGRAMMING MODE
3=REMOTE DOWNLOAD
Содержание MS-10UD Series
Страница 54: ...Installation ANN BUS Audio Panel 54 MS 5UD and MS 10UD Series Manual P N 52626 B1 6 30 2009 Notes ...
Страница 108: ...Programming Maintenance Programming Level 108 MS 5UD and MS 10UD Series Manual P N 52626 B1 6 30 2009 Notes ...
Страница 158: ...158 MS 5UD and MS 10UD Series Manual P N 52626 B1 6 30 2009 Z Z Index ...
Страница 160: ...World Headquarters 1 Firelite Place Northford CT 06472 1653 USA 203 484 7161 fax 203 484 7118 www firelite com ...