ES-200X Series Manual —
P/N LS10131-000FL-E:C 7/25/2018
97
Master Programming Level
Programming
ANN-RLY Options
Pressing
2
for
Module Options
while viewing the ANN-BUS Address Screen when the ANN-RLY option is
selected, will cause the following screen to be displayed:
The ANN-RLY module provides ten Form-C relays which can be programmed for various functions. The initial screen displays Relays 1
through 3. Pressing the down arrow key will display the remaining relays for this module.
To program any of the ANN-RLY relays, while viewing the appropriate ANN-RLY Option screen, press the number key corresponding
to the relay to be programmed. Following is a list of the available programming options for each relay:
•
Alarm
•
Supervisory
•
Supervisory AR
•
Trouble
•
Comm Fail
•
Process Mon
•
Process Mon AR
•
AC Loss
•
Hazard
•
Medical
•
Silenceable Alarm
•
Zone Active XXX (where XXX = programmed zone 000 to 099)
•
Carbon Monoxide
Auto-Configure
The ANN-BUS Auto-Configure features allows the programmer to quickly bring all installed ANN-BUS
modules online on the selected ANN-BUS. The software will search the selected circuit for all ANN-BUS
modules and automatically program the device type and address into the system. For the Auto-Configure to
work, the selected ANN-BUS must be enabled, the annunciators must be connected/powered, and a unique
address must be set on each annunciator. Pressing
3
while viewing ANN-BUS (X) Screen #1 will begin the
Auto-Configure process and cause the following screen to be displayed:
Class A
This option applies to the Primary ANN-BUS only. The primary ANN-BUS can be configured for Class A
wiring. If wired in Class A configuration, press
1
on ANN-BUS Primary Screen #2 to select
Class A Yes
.
Each press of the
1
key toggles between
Class A No
and
Class A Yes
.
ANN-BUS Options
Three ANN-BUS modules have more programming options. Pressing 3 while viewing the Annunciators
screen will display the following.
ANN XXX
1=ENABLED YES
2=MODULES INSTALLED
3=AUTO-CONFIGURE
ANN XXX Screen #2
ANN-RLY - ADDR. X-1
1=RLY 1 ZONE 000
2=RLY 2 ZONE 001
3=RLY 3 ZONE 002
ANN-RLY Options Screen
XXX ANN-BUS
1=ENABLED YES
2=MODULES INSTALLED
3=AUTO-CONFIGURE
(XXX) ANN-BUS Screen #1
ANN-BUS
AUTO-CONGFIGURE
IN PROGRESS
PLEASE WAIT
Auto-Configure Screen
XXX ANN-BUS
1=CLASS A NO
ANN-BUS (XXX) Screen #2
ANN-BUS SELECT
1=PRIMARY
2=SECONDARY
3=ANN-BUS OPTIONS
Annunciator Screen
ANN-BUS
1=ANN-S/PG OPTIONS
2=ANN-LED OPTIONS
3=ANN-80/100 OPTIONS
ANN-BUS Options Screen