ES-200X Series Manual —
P/N LS10131-000FL-E:C 7/25/2018
Appendix C: NFPA Standard-Specific Requirements
The ES-200X has been designed for use in commercial, industrial, and institutional applications and meets the requirements for service
under the National Fire Protection Association (NFPA) Standards outlined in this Appendix. The minimum system components required
for compliance with the appropriate NFPA standard are listed below:
ES-200X Control Panel
Contains the main control board, cabinet (backbox and door), main power supply transformer and power supply.
Batteries
Refer to “Power Supply Calculations” on page 128, for Standby Power Requirements.
Initiating Devices
Connected to one of the control panel's Initiating Device Circuits.
Notification Appliances
Connected to the control panel's Notification Appliance Circuits via a control module.
The following additional equipment is needed for compliance with the NFPA 72 standards listed below:
NFPA 72 NATIONAL FIRE ALARM STANDARDS FOR:
NFPA 72 Central Station Service (Protected Premises Unit) or Remote Station Service
Onboard Digital Alarm Communicator Transmitter for connection to a compatible listed Central Station DACR or Protected
Premises Receiving Unit. This unit must be installed as outlined in “Components” on page 16.
OR
4XTMF Transmitter Module for connection to the RS82 Remote Station Receiver. See Figure C.2, “Remote Station
Connection Using 4XTMF Module,” on page 140, for installation instructions for this unit.
NFPA 72 Auxiliary Fire Alarm System
4XTMF Transmitter Module for connection to a compatible listed Local Energy Municipal Box. This unit must be installed as illustrated
in the section titled “4XTMF Transmitter Module Installation” on page 31 and as outlined in Figure C.1, “Municipal Box Connected to
4XTMF Transmitter Module” on page 139.
NFPA 72 Proprietary Fire Alarm System
ES-200X Alarm, Trouble and Supervisory contacts connected to Transmitter(s). See Figure C.3, “Proprietary Protective Signaling Sys-
tem,” on page 141, for installation instructions for this unit.
NFPA 72 Auxiliary Fire Alarm System
All connections are power-limited and supervised. This application is not suitable for separate transmission of sprinkler supervisory or
trouble conditions.
Notes:
1.
3 ohms maximum loop resistance allowed for wiring from control panel to Municipal Box.
2.
Cut JP3 on the ES-200X main circuit board to supervise placement of 4XTMF module and circuit.
3.
Cut JP2 on the ES-200X main circuit board to enable FACP Supervisory relay.
4.
Refer to “4XTMF Transmitter Module Installation” on page 31 for detailed information.
Figure C.1 Municipal Box Connected to 4XTMF Transmitter Module
FIRE
Gamewell Model M34-56 Local
Energy Municipal Box
Polarities shown in alarm condition
+
Nonpower-limited
Municipal Box Circuit
+
-
-
4XTMF