Master Programming Level
Programming
A flashing cursor will appear in the position of the first asterisk to the left. The programmer keys in the three digit module address, such
as
012
. When the last digit is keyed-in, if the selected address has
not
been added to programming, a screen showing information about a
device that is installed with a lower address, closest to the selected address, will be displayed. If no modules are installed on the loop, the
following screen will be displayed:
If the selected address has been added to programming but a module (such as a monitor module) with the selected address is not physi-
cally installed on the SLC or has a communication fault, the following screen will be displayed:
If the selected address has been added to programming and a module (such as a monitor module) with the selected address is physically
installed on the SLC and is communicating with the control panel, the following screen will be displayed:
To change the programming for the displayed module, press the keyboard down arrow key to view the following Edit Monitor screens.
In
the preceding example:
Normal - indicates that the module with the selected address is physically installed on the SLC and communicating with the
control panel (enabled)
<ADJ><NOUN> - represents the adjective and noun, which have been programmed, describing the location of the displayed
device
ZNNN - represents the first of five possible software zones that the module is assigned to (NNN = the three digit zone number
from 000 - 099)
1M012 - represents the Loop, Device type and Device address (1 = SLC Loop, M = Module and 012 = Module Address 012)
W or * - indicates whether or not the device is programmed for Walktest (W = programmed for walktest, * = not programmed for
walktest).
X or * - indicates whether or not the device is wireless (X = wireless, * = wired).
If the selected address corresponds to a control module, a screen displaying information about the control module with the selected
address will be displayed as shown in “Edit Module Screen for Control Modules” on page 65.
If the selected address corresponds to a monitor module, a screen displaying information about the module with the selected address will
be displayed as illustrated in the following:
Enable/Disable Module
To Enable or Disable the monitor module, press the
1
key while viewing the Edit Module Screen #2. Each press of the key will toggle the
screen between
Enabled Yes
and
Enabled No
. If
Enabled No
is selected, the module will not be polled by the control panel, preventing
the module from reporting alarms and troubles to the panel. The control panel will indicate a system trouble condition and the Disable
LED with turn on if any devices are disabled.
NO MODULE
INSTALLED
Edit Module Screen
TROUBL MONITOR
<ADJ><NOUN>
ZNNN
1M012
NORMAL MONITOR
<ADJ><NOUN>
ZNNN
W 1M012
NORMAL MONITOR
<ADJ><NOUN>
ZNNN
1M012
EDIT MONITOR 1M012
1=ENABLED YES
2=TYPE MONITOR
Edit Monitor Screen #2
Edit Monitor Screen #3
EDIT MONITOR 1M012
1=WALKTEST YES
2=ZONE ASSIGNMENT
000
Edit Monitor Screen #4
EDIT MONITOR 1M012
1=ADJECTIVE/NOUN
2=DESCRIPTION
Edit Monitor Screen #5
EDIT MONITOR 1M012
1=PRE-SIGNAL NO
WIRELESS NO