72
ES-200X Series Manual —
P/N LS10131-000FL-E:C 7/25/2018
Programming
Master Programming Level
•
Language
: This option allows the user to switch between English and French language text on the panel display.
•
Charger Enable
: This option allows the user to install an external battery charger.
•
4XTM Supervision
: This feature enables supervision of an installed 4XTMF Transmitter Module.
•
Remote Sync Enable
: This feature controls the activation of notification appliances in such a way that all devices will turn on and
off at exactly the same time.
Pressing
2
for System Setup, while viewing Programming Screen #2, will cause the following screens to be
displayed:
Function Keys
The ES-200X keypad has 4 programmable function keys. These keys can be programmed to allow rapid disable/enable of various fire
panel inputs and outputs during scheduled maintenance. pressing any function key results in a trouble signal at the panel. Pressing
1
on
System Setup Screen #1 displays the following:
Select
1
,
2
,
3
, or
4
to program the corresponding Function Key. The following screens display for each
Function Key where “(X)” represents the number of the key chosen.
To Enable or Disable the Function Key, press the
1
key while viewing the Function Keys Screen #1. Each press of the key will toggle the
screen between
Key Enabled Yes
and
Key Enabled No
.
Pressing
2
key while viewing the Function Keys Screen #1 allows the user to select individual zones that the Function Key will control.
Pressing
3
assigns all zones to the selected Function Key.
Each function key can be assigned to control any of the 4 onboard NAC circuits on the ES-200X. By pressing the
2
key while viewing
the Function Keys Screen #2 the following screen displays, allowing the user to select the desired NAC circuit(s).
Pressing
1
,
2
,
3
, or
4
toggles the screen between
Yes
(controlled by function key) and
No
(not controlled by function key) for each
onboard NAC circuit.
The Remote Synchronization (TB8 on the FACP’s main circuit board) can also be disabled through pro-
gramming of a function key. To disable remote synchronization, press the
3
key while viewing the Function
Keys Screen #2. Each press of the key will toggle the screen between
Rem Sync Disb Yes
and
Rem Sync
Disb No
.
PROGRAMMING
1=LOOP SETUP
2=SYSTEM SETUP
3=FUTURE USE
Programming Screen #2
SYSTEM SETUP
1=FUNCTION KEYS
2=BANNER
3=TIME-DATE
System Setup Screen #1
SYSTEM SETUP
1=TIMERS
2=NAC
3=RELAYS
System Setup Screen #2
SYSTEM SETUP
1=CANADIAN OPT. OFF
2=WATERFLOW SIL. NO
3=MNS OVERRIDE NO
System Setup Screen #3
SYSTEM SETUP
1=AUX POWER
2=TROUBLE REM 24HR
3=LANGUAGE ENGLISH
System Setup Screen #4
SYSTEM SETUP
1=CHARGER ENAB YES
2=4XTM SPV ENAB NO
3=REM SYNC ENAB YES
System Setup Screen #5
FUNCTION KEYS
1=F1 3=F3
2=F2 4=F4
Function Keys Screen
FUNCTION KEYS
1=F1 3=F3
2=F2 4=F4
Function Keys Screen
Function Keys Screen #1
Function Keys Screen #2
F(X) KEY OPERATION
1=KEY ENABLED NO
2=ZONES
3=ALL ZONES
F(X) KEY OPERATION
1=NACS
2=REM SYNC DISB NO
F(X) NACS
1=NAC 1 Y 3=NAC 3 N
2=NAC 2 Y 4=NAC 4 N
Function Keys Screen
F(X) KEY OPERATION
1=NACS
2=REM SYNC DISB YES
Function Keys Screen #2
Содержание ES-200X
Страница 137: ...ES 200X Series Manual P N LS10131 000FL E C 7 25 2018 137 Notes ...
Страница 164: ...164 ES 200X Series Manual P N LS10131 000FL E C 7 25 2018 ...
Страница 166: ...Cut along dotted line ...
Страница 168: ...One Fire Lite Place Northford CT 06472 1601 USA USA Phone 203 484 7161 Canada Phone 905 856 8733 www firelite com ...