ES-200X Series Manual —
P/N LS10131-000FL-E:C 7/25/2018
129
Calculating the System Current Load
Power Supply Calculations
Device Type
Calculation Column 1
Primary (AC) Power Source
Fire Alarm Current (amps)
Calculation Column 2
Secondary (Battery) Power Source
Fire Alarm Current (amps)
Calculation Column 3
Secondary (Battery) Power Source
Standby Current (amps)
Qty
X[current draw]=
Total
Qty X [current draw]=
Total
Qty
X [current draw]=
Total
Main Circuit Board
1
1
X[0.257]=
1
X[0.141]=
IPOTS-COM Communicator
[ ]
X[0.041]=
[ ]
X[0.041]=
[ ]
X[0.040]=
CELL-MOD/CAB-FL
[ ]
X[0.100]=
[ ]
X[0.100]=
[ ]
X[0.055]=
PWRMOD24
N/A
[ ]
X[0.008]=
[ ]
X[0.007]=
ANN-80
[ ]
X[0.040]=
[ ]
X[0.040]=
[ ]
X[0.015]=
ANN-100
[ ]
X[0.025]=
[ ]
X[0.025]=
[ ]
X[0.020]=
ANN-(R)LED
[ ]
X[0.068]=
[ ]
X[0.068]=
[ ]
X[0.028]=
ANN-RLY
[ ]
X[0.075]=
[ ]
X[0.075]=
[ ]
X[0.015]=
ANN-I/O
[ ]
X[0.200]=
[ ]
X[0.200]=
[ ]
X[0.035]=
ANN-S/PG
[ ]
X[0.045]=
[ ]
X[0.045]=
[ ]
X[0.045]=
ECC-FFT
N/A
[ ]
X[0.230]=
[ ]
X[0.120]=
4XTMF
[ ]
X[0.011]
2
=
[ ]
X[0.011]=
[ ]
X[0.005]=
4-wire Detector Heads
[ ]
X[ ]=
[ ]
X[ ]
3
=
[ ]
X[ ]=
Power Supervision Relays
4
[ ]
X[0.025]=
[ ]
X[0.025]=
[ ]
X[0.025]=
CP350, CP355
maximum alarm draw
for all devices =
0.400
maximum alarm draw
for all devices =
0.400
[ ]
X[0.00030]=
SD350, SD355, SD365
[ ]
X[0.00030]=
SD355CO
[ ]
X[0.00030]=
SD350T, SD355T, SD365T
[ ]
X[0.00030]=
AD350, AD355
[ ]
X[0.00030]=
H350, H355, H365
[ ]
X[0.00030]=
H350R, H355R, H365R
[ ]
X[0.00030]=
H355HT, H365HT
[ ]
X[0.00030]=
D350P, D350PL
[ ]
X[0.00030]=
D350RP, D350RPL
[ ]
X[0.00030]=
B501BH, B501BHT
5
[ ]
X[0.001]=
B224RB Relay Base
[ ]
X[0.00050]=
B224BI Isolator Base
[ ]
X[0.00045]=
MMF-300
[ ]
X[0.00040]=
MMF-300-10
[ ]
X[0.00350]=
MDF-300
[ ]
X[0.00075]=
MMF-301
[ ]
X[0.000375]=
MMF-302
[ ]
X[0.00027]=
MMF-302-6
[ ]
X[0.00200]=
BG-12LX
[ ]
X[0.00030]=
CMF-300
[ ]
X[0.00039]=
CMF-300-6
[ ]
X[0.00225]=
CRF-300
[ ]
X[0.00027]=
CRF-300-6
[ ]
X[0.00145]=
I300
[ ]
X[0.00040]=
ISO-6
[ ]
X[0.00045]=
W-GATE
[ ]
X[0.040] or [0.024]
6
NAC #1
7
[ ]
X[ ]=
[ ]
X[ ]=
[ ]
X[ ]=
[ ]
X[ ]=
[ ]
X[ ]=
[ ]
X[ ]=
[ ]
X[ ]=
[ ]
X[ ]=
FCPS (remote sync)
[ ]
X[0.02]=
[ ]
X[0.0217]=
Current Draw from TB3
[ ]
[ ]=
[ ]
[ ]=
[ ]
[ ]=
Sum each column for totals AC Powered,
Fire Alarm Load
8
=
Battery Powered,
Fire Alarm Load
9
=
Battery Powered,
Standby Load
10
=
Table 9.3 System Current Load Calculations
1
Main board with display only.
2
If using the Reverse Polarity Alarm output, add 0.005 amps; if using the Reverse Polarity Trouble output, add another 0.005 amps.
3
Refer to the Device Compatibility Document for standby current.
4
Must use compatible listed Power Supervision Relay.
5
Maximum alarm current for each sounder base is 0.015 amps which must be supplied by aux. 24VDC source.
6
When powered by an external source, use 0.040A. When powered by the SLC, use 0.024A.
7
If using Gentex brand NACs, the max number of devices for each NAC output is 35. The “UL Max” current rating, published in their data sheets, must be
used in order to maintain performance under low battery conditions with the maximum wire resistances shown in Table D.2 on page 144.
8
Total Alarm current load cannot exceed 3.0 amps or 6.0 amps only when the PWRMOD24 option module is installed.
9
When AC power is initially applied to the panel and the battery is not fully charged, an initial charge current of up to 5.3 amps may be observed at the
battery. This high current is only applied for a very short duration (milliseconds) and does not affect system load or battery size calculations.
10 Total Standby current load cannot exceed 2.25 amps.