Programming Using the HFSS Programming Tool
Programming Overview
FCP-75 Manual —
P/N:LS10147-003FK-E:A 3/17/2021
75
8.2.4 Mapping LED Points
Figure 8.6 is a simple example showing how LED points are mapped to zones and Output Groups. Typically you would create two Output
Groups for each zone, one for alarms and one for troubles. (LED points are available when Models FIK-5865-3/4 and/or FIK-5880 are used
with the system).
Figure 8.6 Example of LED Points Mapped to Output Groups (applies to Models FIK-5865-3/4 and FIK-5880)
8.3 Programming Using the HFSS Programming Tool
You can use the HFSS Programming Tool to program the control panel onsite (personnel will need to be onsite during the upload or down-
load process). HFSS is a software package that lets you easily program the control panel using a Windows-based computer. HFSS is needed
for Mapping. When using HFSS, you can set up the programming options for the panel, save the options in a file, then download the file to
the panel. You can connect to the control panel directly using the onboard USB or Ethernet. Updates are available at www.fike.com.
8.4 Programming Using an Annunciator
You can program the control panel from a system annunciator, using either the control panel’s on-board annunciator, FIK-RA100, FIK-
RA2000, or FIK-RA1000R remote annunciators.
The following subsections describe programming basics, including a description of editing keys available for programming and how to move
through programming Menus. Section 9 contains specific information about individual programming options.
NOTE:
Mapping cannot be programmed through the on-board and remote annunciators. Mapping is only available through the HFSS
Programming Tool up/downloading software.