FCP-75 Manual —
P/N LS10147-003FK-E:A 3/17/2021
15
Section 3: Before You Begin Installing
This section of the manual is intended to help you plan your tasks to facilitate a smooth installation. Please read this section thoroughly, espe-
cially if you are installing an FCP-75 panel for the first time.
3.1 Inventory
When the FCP-75 shipment is received, check that all the parts have been included in the shipment. The shipment consists of one of each of
the following:
•
main circuit board with display
•
backbox with door
•
plastic bag containing two keys, screws, cables, and ten 4.7K ohm end-of-line resistors
•
manual
3.2 Environmental Specifications
It is important to protect the FCP-75 control panel from water. To prevent water damage, the following precautions should be FOLLOWED
when installing the units:
•
Intended for indoor use in dry locations only.
•
Do not mount directly on exterior walls, especially masonry walls (condensation).
•
Do not mount directly on exterior walls below grade (condensation).
•
Protect from plumbing leaks.
•
Protect from splash caused by sprinkler system inspection ports.
•
Do not mount in areas with humidity-generating equipment (such as dryers, production machinery).
When selecting a location to mount the FCP-75 control panel, the unit should be mounted where it will NOT be exposed to temperatures out-
side the range of 0°C-49°C (32°F-120°F) or humidity outside the range of 10%-93% at 30°C (86°F) noncondensing.
3.3 Software Downloads
In order to supply the latest features and functionality in fire alarm and life safety technology to our customers, we make frequent upgrades
to the embedded software in our products. To ensure that you are installing and programming the latest features, we strongly recommend that
you download the most current version of software for each product prior to commissioning any system. Contact Technical Support with any
questions about software and the appropriate version for a specific application. The HFSS Programming Tool is available at wwwfike.com.
3.4 Electrical Specifications
Table 3.1 list the terminal block on the FCP-75 as well as a description of the each individual terminal and their respective electrical rating.
For location of the terminals refer to Figure 3.2. See also Section 4 for installation.
Terminal No.
Label
Description
Rating
Group
Individual
Voltage
Current
Terminal Block 3
TELCO 1
RING
Phone Line 1 Telco Ring
TIP
Phone Line 1 Telco Tip
PHONE 1
RING
Phone Line 1 Phone Ring
TIP
Phone Line 1 Phone Tip
TELCO 2
RING
Phone Line 2 Telco Ring
TIP
Phone Line 2 Telco Tip
PHONE 2
RING
Phone Line 2 Phone Ring
TIP
Phone Line 2 Phone Tip
Terminal Block 2
RELAY 1
NO
Normally open relay contact
27.4 VDC
2.5 A, resistive
COM
Common terminal
NC
Normally closed relay contact
RELAY 2
NO
Normally open relay contact
27.4 VDC
2.5 A, resistive
COM
Common terminal
NC
Normally closed relay contact
TROUBLE
NO
Normally open relay contact
27.4 VDC
2.5 A, resistive
COM
Common terminal
NC
Normally closed relay contact
SLC IN
–
Used for Class A installations
32 VDC
100 mA
+
Table 3.1 Terminal Descriptions and Electrical Specifications