Basic Operation
System Operation
FCP-75 Manual —
P/N:LS10147-003FK-E:A 3/17/2021
103
2.
Select 5 for Communicator Test. The screen will display “Manual communicator test started”. When the test is completed, you will be
returned to the <Test Menu>. A manual communicator test requires that at least one daily test in the network be enabled in
communicator programming.
3.
The Manual communicator test will be communicated out both Phone Lines and Ethernet paths if they are all programmed. Each
manual communicator test will alternate between one of the Phone Line paths and one of the AlarmNet paths.
10.4.8 Manual AlarmNet Registration
1.
From the Main Menu, press 1 for System Tests.
2.
Select 8 for Register AlarmNet. The screen will display and ask for confirmation. Feedback will be given if the command was sent or
not.
10.4.9 Silence Alarms or Troubles
Press SILENCE and enter your code or rotate the key at the prompt. If an external silence switch has been installed, activating the switch will
silence alarms or troubles. If you are already using system Menus when you press SILENCE, you will not need to enter your code or rotate
the key.
10.4.10 Reset alarms
Press RESET and enter your code or rotate the key at the prompt. If an external reset switch has been installed, activating the switch will
reset alarms. If you are already using system Menus when you press RESET, you will not need to enter your code or rotate the key.
Reset Communicator
This options allows the user to Reset the Communicator. The LCD will display:
“Communicator Reset in progress… Please Wait“
You will be returned to the Main Menu when the reset is complete.
The communicator is not allowed to be reset when alarms or supervisories are active. Communicator reset is not allowed if any of the follow-
ing are active:
•
Fire Alarm
•
Fire Supervisory
•
Fire Pre-Alarm
•
CO Alarm
•
CO Supervisory
10.4.11 Check Detector Sensitivity Through Point Status
The control panel constantly monitors smoke detectors to ensure that sensitivity levels are in compliance with NFPA 72.
If sensitivity for a detector is not in compliance, the panel goes into trouble, generating a CAL TRBLE condition. A detector enters a CAL
MAINT state to indicate that it is approaching an out of compliance condition (but is currently still in compliance).
When a CAL TRBLE condition occurs, the central station receives a detector trouble report (“373” and the zone or point for Contact ID for-
mat; “FT” and the zone or point in SIA format).
To check sensitivity for an individual detector, follow the steps below:
1.
From the Main Menu, press 2 for Point Functions.
2.
Press 2 for Point Status.
3.
Select the module where the point you want to check is located.
4.
Enter the number of the point you want to check and press ENTER.
NOTE 1:
Alarm and trouble signals that have been silenced but the detector remains un-restored will un-silence every 4 or 24 hours depending
on user selection until it is restored.
NOTE 2:
Multi-Site displays do not allow for silencing multiple sites. Pressing SILENCE will only locally silence the PZT built into the
annunciator.
NOTE:
Multi-Site displays do not allow for resetting multiple sites.