background image

FCP-75 Manual —  

P/N LS10147-003FK-E:A  3/17/2021

127

Appendix A: Compatible Devices

A.1  Notification Appliances

For proper operation, you must use polarized devices with a 4.7k ohm EOL resistor on each loop. All supervised notification appliances used 
with the control panel must be polarized.

Table below lists notification appliances compatible with the fire alarm control panel. Appliances which can be 
synchronized indicate the type of SYNC available in the columns marked Audio and Visual.

NOTE:

Not all devices can use the Sync feature, be sure to check table below to ensure the device you have chosen will work with this feature. 

This control is UL listed for panel wide Synchronization.

Manufacturer

Model

Audio

Visual

Type

AMSECO

SH24W-153075

x

x

Horn/Strobe

SAD24-153075

x

Strobe

SAD24-75110

x

Strobe

SL24W-75110

x

Strobe

SL24C-3075110

x

Strobe

SLB24-75

x

Strobe

RSD24-153075

x

Strobe

RSD24-75110

x

Strobe

SH24W-75110

x

x

Horn/Strobe

SH24W-3075110

x

x

Horn/Strobe

SHB24-75

x

x

Horn/Strobe

SCM24W-153075

x

Chimes/Strobe

SCM24W-75110

x

Chimes/Strobe

SCM24C-3075110

x

Chimes/Strobe

SCM24C-177

x

Chimes/Strobe

H24W

x

Horn

H24R

x

Horn

FCI

S2415-FC

x

Strobe

S241575-FC

x

Strobe

S2430-FC

x

Strobe

130-3117C

x

Mini Horn

130-3147C

x

Mini Horn

BLV-6

x

Vibrating Bell

BLV-10

x

Vibrating Bell

BLVCH

x

Vibrating Chime

H12/24-FC

x

Horn

H12/24W-FC

x

Horn

H12/24K-FC

x

Horn

HC12/24-FC

x

Horn

Table A.1 Compatible Notification Appliances 

Содержание FCP-75

Страница 1: ...A P N LS10147 003FK E A ECN 151526 Document LS10147 003FK E 3 17 2021 Rev Addressable Fire Alarm Control Panel FCP 75 Instruction Manual ...

Страница 2: ...hes a predetermined level Rate of rise heat detectors may be subject to reduced sensitivity over time For this reason the rate of rise feature of each detector should be tested at least once per year by a qualified fire protection specialist Heat detectors are designed to protect property not life IMPORTANT Smoke detectors must be installed in the same room as the control panel and in rooms used b...

Страница 3: ...r to any drilling filing ream ing or punching of the enclosure When possible make all cable entries from the sides or rear Before making modifications verify that they will not interfere with battery transformer or printed circuit board location Do not tighten screw terminals more than 9 in lbs Over tightening may damage threads resulting in reduced terminal contact pressure and difficulty with sc...

Страница 4: ...il us Please include the following information Product name and version number if applicable Printed manual or online Help Topic Title for online Help Page number for printed manual Brief description of content you think should be improved or corrected Your suggestion for how to correct improve documentation Send email messages to FikeElectSupport fike com or call 800 979 3453 x21 in US or 816 229...

Страница 5: ...17 3 7 Calculating Current Draw and Standby Battery 17 3 7 1 Current Draw Worksheet Requirements 17 3 7 2 Current Draw Worksheet for Fike IDP SLC Devices 18 Maximum Battery Standby Load 20 Section 4 Control Panel Installation 21 4 1 Mounting the Control Panel Cabinet 21 4 1 1 Preventing Water Damage 21 4 1 2 Removing the FCP 75 Assembly from the Housing 21 4 2 AC Power Connection 21 4 3 Battery Po...

Страница 6: ...ir Products 48 4 15 5 Transmitter Activated by Dry Contacts 50 Section 5 Networking Common Communicator List 51 5 1 Network System Hardware Features 51 5 1 1 Networked Panels 51 5 1 2 Wiring Options to Connect Networked Panels 51 5 2 Direct Connect Wiring Option 51 5 3 FIK NIC Wiring Options 51 5 3 1 Fiber Loop Modules 52 FIK NIC KIT Mounting Kit 53 5 3 2 FIK NIC Installation 53 Unshielded Twisted...

Страница 7: ...sing an Annunciator 75 8 4 1 Entering Exiting the Program Menu 76 8 4 2 Moving through the Menus 76 8 4 3 Selecting Options and Entering Data 76 8 5 Programming Menu Quick Reference 77 Section 9 Programming 84 9 1 UL 864 Programming Requirements 84 9 2 Modules 84 9 2 1 Edit Modules 84 Editing Module ID 84 Naming Modules 84 Changing Module Options 85 9 2 2 Adding a Module 85 9 2 3 Deleting a Module...

Страница 8: ...e Enable NACs by Template 101 Disable Enable NACs by Group 101 Disable Enable Zone Points 101 Disable Enable Point 101 Inhibit Output Group 101 10 4 3 View Event History 102 To clear the event history 102 10 4 4 Conduct a Fire Drill 102 10 4 5 Conduct an Indicator Test 102 10 4 6 Conduct a Walk Test 102 10 4 7 Conduct a Communicator Test 102 10 4 8 Manual AlarmNet Registration 103 10 4 9 Silence A...

Страница 9: ...ice Locater 123 12 2 2 SLC Multi Locater 123 12 2 3 I O Point Control 124 12 3 Earth Fault Resistance 124 Section 13 Installation Records 125 13 1 IDP SLC Device Point Record 125 Appendix A Compatible Devices 127 A 1 Notification Appliances 127 A 2 Four Wire Smoke Detectors Devices UL Listed 136 A 3 Door Holders UL Listed 137 A 4 Relays UL Listed 137 A 5 Compatible 520Hz Signaling Speakers 138 A 6...

Страница 10: ...2 FCP 75 panels connected Network support for up to 32 Sites Each building is referred to as a site Panels can be interconnected using CLASS B or CLASS A topology Use the FIK NIC Network Interface Card to create a network Copper wire or fiber optic cable panel connectivity can be used within the same networked system The network architecture provides true peer to peer capability allowing network s...

Страница 11: ...iance Circuits Auxiliary power Up to 8 per FCP 75 system FIK RA100 and FIK RA1000R LCD Annunciator 4 x20 Remote LCD annunciator can be used in any combination up to a total of 8 devices on one panel FIK RA2000 LCD Annunciator 4 x 40 Remote LCD annunciator can be used in any combination up to a total of 8 devices on one panel FIK 5865 3 and FIK 5865 4 LED Annunciator LED annunciator can display up ...

Страница 12: ...etwork This number must not exceed 5 0 Since this product has an REN of 1 0A the number of devices is limited The REN number is embedded in the FCC registration number as 10A 5 If this equipment FCP 75 causes harm to the telephone network the telephone company will notify you in advance that temporary discontinuance of service may be required But if advance notice isn t practical the telephone com...

Страница 13: ...etectors 2 2 2 Requirements for Central Station Fire Alarm Systems 1 Use both phone lines Enable phone line monitors for both lines 2 You must program a phone number and a test time so that the FCP 75 shall automatically initiate and complete a test signal transmission sequence to its associated receiver at least once every 6 hrs The AC Loss Hours option must be set from 1 3 hours 3 If using wired...

Страница 14: ...nfiguration to meet the NFPA requirements Model Module Description Local Releasing Remote Station Auxiliary Central Station Emergency Signaling 0067000 Main board Y Y Y Y Y Y FIK 5496 NAC expander O Y O O O O 5220 Direct connect module N N N Y N O FIK NIC Network card O O O O O O FIK FML FSL Fiber module O O O O O O Y YES N NO O OPTIONAL Table 2 1 NFPA Requirements for FCP 75 ...

Страница 15: ...n order to supply the latest features and functionality in fire alarm and life safety technology to our customers we make frequent upgrades to the embedded software in our products To ensure that you are installing and programming the latest features we strongly recommend that you download the most current version of software for each product prior to commissioning any system Contact Technical Sup...

Страница 16: ... the inductive reactance of a speaker or bell can also be reduced by running the wire through ferrite shield beads or by wrapping it around a ferrite toroid Figure 3 1 Wire Routing Example Terminal Block 2 SLC OUT SLC terminals 32 VDC 100 mA SLC PROG Used for programming SLC Detectors 32 VDC 100 mA SBUS SBUS Power 27 4 VDC 0 5 A A SBUS Communication 5 VDC 100 mA B NAC1 Notification Appliance Circu...

Страница 17: ...this information in the Current Calculation Worksheet at Line A 2 Add up the current draw for all auxiliary devices and record in the table at Line B 3 Add up all notification appliance loads and record in the table at Line C 4 For notification appliance circuits and auxiliary devices not mentioned in the manual refer to the device manual for the current ratings 5 Make sure that the total alarm cu...

Страница 18: ...6 with Relay None included with FIK 2351R FIK M500R7 Addressable SLC Modules FIK M500M Standby Alarm 0 375 mA mA mA FIK M501M mA mA FIK PULL SA FIK PULL DA FIK M500DM Standby Alarm 0 75mA mA mA FIK IM 10 Standby Alarm 3 5mA mA mA FIK M500S SLC Standby 0 375mA Alarm 0 375mA mA mA Aux Pwr Standby 1 7mA mA Alarm 7mA mA FIK SC 6 SLC Standby 2 25mA Alarm 2 25mA mA mA Aux Pwr Standby 8mA mA Alarm 20mA m...

Страница 19: ...A FIK RPS1000 Power Supply Standby Alarm 10 mA mA mA FIK 5865 4 LED Annunciator with reset and silence switches 8 max Standby 35 mA mA Alarm 145 mA mA FIK 5865 3 LED Annunciator Standby 35 mA mA Alarm 145 mA mA FIK 5880 LED I O Module Standby 35 mA mA Alarm 200 mA mA FIK 5883 Relay Interface 32 max Standby 0 mA mA Alarm 220 mA 22 mA per relay mA FIK NIC Network Interface Card 1 Max Standby Alarm 2...

Страница 20: ... Max Load for 60hrs Standby 5 minutes Alarm 7AH 221mA 85mA 18AH 675mA 250mA 33AH 1 1A 450mA Table 3 4 Maximum Battery Standby Load NOTE Required for NFPA 72 Auxiliary Protected Fire Alarm systems for Fire Alarm Service City Box and Remote Station Protected Fire Alarm systems Polarity Reversal and Digital Alarm Communicator Transmitter DACT WARNING BATTERIES FIKE DOES NOT SUPPORT THE USE OF BATTERI...

Страница 21: ...to the fire system can be caused by moisture entering the cabinet through the conduits Conduits that are installed to enter the top of the cabinet are most likely to cause water problems Installers should take reasonable precautions to prevent water from entering the cabinet Water damage is not covered under warranty 4 1 2 Removing the FCP 75 Assembly from the Housing If it should ever be necessar...

Страница 22: ... current load calculation see Section 3 7 Maximum battery charging current 3 1 Amps Wire batteries in series to produce a 24 volt equivalent Do not parallel batteries to increase the AH rating The following steps and diagram explain how to connect the batteries 1 Connect the black wire from the control panel negative battery terminal to the negative side of Battery 2 2 Connect the jumper wire prov...

Страница 23: ...es If mounting onto drywall the accessory cabinet must be mounted onto 3 4 inch plywood This is necessary because the weight of the batteries inside the accessory cabinet could cause the cabinet to pull away from the drywall When mounting on concrete especially when moisture is expected attach a piece of plywood to the concrete surface and then attach the RBB cabinet to the plywood If using the ba...

Страница 24: ...es and the types of wiring configurations Class B 4 4 1 Calculating Wiring distance for SBUS modules The following instructions will guide you in determining the type of wire and the maximum wiring distance that can be used with control panel SBUS accessory modules To calculate the wire gauge that must be used to connect SBUS modules to the control panel it is necessary to calculate the total wors...

Страница 25: ...880 LED I O Module 250 amps FIK 5865 LED Fire Annunciator 200 amps FIK 5496 NAC Expander 010 amps FIK NIC Network Interface Card 021 amps SK F485C Fiber Converter 125 amps Table 4 1 SBUS Device Current Draw Wiring Distance SBUS Modules to Panel Total Worst Case Current Draw amps 22 Gauge 18 Gauge 16 Gauge 14 Gauge 0 100 1852 ft 4688 ft 6000 ft 6000 ft 0 200 926 ft 2344 ft 3731 ft 5906 ft 0 300 617...

Страница 26: ...tions Figure 4 8 illustrates Class B configuration Figure 4 8 SBUS Class B Wiring 4 5 FIK RA100 Remote Annunciator Installation The optional Model FIK RA100 Remote Annunciator is shown in Figure 4 9 The FIK RA100 can be surface or flush mounted Up to 8 FIK RA100s can be added to the FCP 75 system in any combination Figure 4 9 Model FIK RA100 Remote Annunciator Front View FIK RA100 Current Draw 2 x...

Страница 27: ... will add the module automatically see Section 8 1 You can also add it manually see Section 9 2 2 Select a name if desired 4 5 1 Mounting the FIK RA100 This section of the manual describes mounting the remote annunciator The annunciator can be flush or surface mounted Flush Mounting This section of the manual describes flush mounting Follow these steps to flush mount the FIK RA100 1 The back box d...

Страница 28: ... Figure 4 11 Back Box Knockout Locations 3 Wire the Annunciator board to the main control panel See Figure 4 8 4 Attach the annunciator and door assembly to back box as shown in Figure 4 12 using the supplied screws Figure 4 12 Attaching Annunciator Door Assembly to Backbox wire knockouts wire knockouts wire knockouts ...

Страница 29: ...Place a level on top of the back box with the back box level insert the rest of the mounting screws Figure 4 13 Back Box Surface Mount Holes 3 Run wires to the control panel 4 Place the trim ring over the back box as shown in Figure 4 14 Figure 4 14 Installing Trim Ring 5 Attach the Door assembly to the back box using the screws provided 6 After the annunciator wiring to the panel has been complet...

Страница 30: ...the FCP 75 system Figure 4 16 Model FIK RA1000R Remote Annunciator Front View FIK RA1000R installation involves the following steps 1 Make sure the power is off at the panel 2 Mount the FIK RA1000R in the desired location see Section 4 6 1 3 Connect the FIK RA1000R to the panel see Section 4 4 Use the dipswitches on the back of the FIK RA1000Rto assign an ID to the FIK RA1000R see Section 4 11 1 5...

Страница 31: ...or bezel See Figure 4 18 for location of the set screws Figure 4 18 Annunciator Back Box and Bezel Details Flush Mounting This section of the manual describes flush mounting You can flush mount with or without an electrical box Flush Mounting with an Electrical Box The FIK RA1000R annunciator can be used with the following types of electrical boxes 4S single gang and double gang If an electrical b...

Страница 32: ...e set screws on the bezel Figure 4 20 Flush Mounting the Back Box Surface Mounting The FIK RA1000R can be mounted directly to a surface or can be attached to a single double or four square electrical box The Model RA 1000TR trim ring kit is available for use when surface mounting 1 Drill holes in the surface to match the screw holes on the back box 2 Fit the trim ring over the back box 3 Attach th...

Страница 33: ...anel see Section 4 7 2 4 Use the DIP switches on the back of the FIK RA2000 to assign an SBUS ID to the FIK RA2000 see Section 4 11 1 5 The FIK RA2000 module must be added to the system through programming JumpStart Auto Programming will add the module automatically see Section 8 1 4 7 1 Mounting the FIK RA2000 This section of the manual describes mounting the remote annunciator The annunciator ca...

Страница 34: ...ure 4 23 Back Box Mounting Holes 2 Remove knockout holes as needed for wires See Figure 4 11 for backbox knockout locations Figure 4 24 Back Box Knockout Locations 3 Wire the annunciator board to the main control panel As described in Section 4 7 2 Mounting Holes Mounting Holes Wire Knockouts Wire Knockouts Wire Knockouts ...

Страница 35: ...ng The Model RA 100TR red trim ring kit is available for use when surface mounting the FIK RA2000 1 Remove the desired knock out See Figure 4 11 2 To properly mount the back box insert a single screw into the key shaped mounting hole Do not tighten all the way See Figure 4 13 Place a level on top of the back box with the back box level insert the rest of the mounting screws Figure 4 26 Back Box Su...

Страница 36: ...FIK RA2000 to the panel as shown in Figure 4 28 Figure 4 28 Model FIK RA2000 Connection to the Panel 4 8 FIK 5824 Serial Parallel Printer Interface Module Installation The FIK 5824 serial parallel printer interface module allows you to connect a printer to the panel Printing is available for real time events detector status and event history FIK 5824 installation involves the following steps 1 Mak...

Страница 37: ... Port Options 6 Select options for the printer as needed for your installation Most printers are parallel 7 If you are using a serial printer use the next screen to select serial port options as required for your printer Refer to your printer manual if you need more information 4 9 FIK 5880 LED Driver Module The FIK 5880 is an LED driver board that can be used in a wide variety of applications inc...

Страница 38: ...shown in Figure 4 32 After the FIK 5880 is connected to the panel it must be added to the system This programming step is described in Section 9 Figure 4 32 FIK 5880 Connection to Main Control Panel Assembly 4 9 3 LED Wiring There are four 12 pin connectors on the FIK 5880 board for connecting LEDs Each LED gets its power from Pin 11 Internal resistors are sized so that there is approximately 10 m...

Страница 39: ... FIK 5880 Board Layout 4 9 4 Dry Contact Wiring The 8 input circuits on the FIK 5880 board are for monitoring switch inputs any type of switch supported by the control panel can be used with the FIK 5880 For example you can use a FIK 5880 to monitor pull stations water flow tamper reset or silence switches NOTE The circuit connected to Open Collector Output last pin on P1 must be current limited s...

Страница 40: ...ble LED The FIK 5865 3 has 30 mappable LEDs only These are arranged as 15 pairs of red typically used for alarm and yellow typically used for trouble LEDs Installation of the FIK 5865 3 and FIK 5865 4 is identical The key switches and the trouble LED follow the behavior of other system annunciators and do not require any installation steps The following sub sections describe how to install the FIK...

Страница 41: ...tion to the FACP 4 10 2 FIK 5865 Mounting Mount the FIK 5865 4 to a standard 4 gang electrical box Mount the FIK 5865 3 to a standard 3 gang electrical box In Figure 4 37 the FIK 5865 4 attached to a 4 gang box is used as an example Figure 4 37 FIK 5865 Mounting Example The FIK 5865 ships with a set of zone description labels that can be inserted into the FIK 5865 board assembly These labels can b...

Страница 42: ... to the system 4 11 1 Assigning Module IDs When installing a hardware module see Table 4 1 for list of compatible SBUS devices you must use the DIP switches on the module to assign an ID to the module Figure 4 39 shows all possible DIP switch positions and their correlation to a numerical ID For example to select ID 2 place DIP switch 2 in the up position Figure 4 39 Possible module addresses Refe...

Страница 43: ...Class B or as Aux power This sec tion of the manual explains how to install conventional notification appliances and how these terminals can be used for auxiliary power 4 13 1 Conventional Notification Appliance This sub section of the manual explains how to install conventional notification appliances for Class A and Class B configurations Class B Notification Wiring You must use an appliance fro...

Страница 44: ...larm condition total current for system must not exceed 2 5A in alarm or 1 0A for all other conditions To install an auxiliary power circuit 1 Wire the NAC circuit s that will be used for auxiliary power See Figure 3 2 for location of NAC circuits 2 Configure the auxiliary power output through programming see Figure 9 5 Door Holder Power Door holder power is intended for fire door applications Whe...

Страница 45: ...y All relays are Form C rated at 2 5 A 27 4 VDC Resis tive Figure 4 44 Location of Conventional Relay Circuits 4 14 1 Common Trouble Relay The control panel has a dedicated Form C trouble relay built into terminals labeled TROUBLE The relay provides a normally open and a normally closed contact The trouble relay will deactivate under any trouble condition Form C rated at 2 5 A 27 4 VDC Resistive 4...

Страница 46: ...arm service The city master box is an enclosure that contains a manually operated transmitter used to send an alarm to the municipal communication center which houses the central operating part of the fire alarm system City Box Standby Current 0 Notification supervision current counted for in control panel draw Alarm Current 1Amp for 1 second Max Voltage 27 4VDC The maximum coil and wire resistanc...

Страница 47: ...ent 100mA Alarm 100mA Max Voltage 27 4VDC To install the 5220 for polarity reversal follow the steps below 1 Locate the knockout on the right side of the control panel cabinet to connect the 5220 using a short piece of conduit must not exceed 20 feet in length 2 Wire the 5220 to the control panel using the four wire pigtail provided as shown in Figure 4 47 This diagram also shows how to connect th...

Страница 48: ...alarm and trouble events to a remote site Alarms will override trouble conditions and it will not be possible to reset the remote indicator until the condition is cleared and the control panel is reset If an alarm condition occurs the alarm relay will close overriding the trouble condition Current 15mA max Operating Voltage 24VDC nominal 27 4 VDC max Resistance 4KΩ Note NAC circuit 1 and Relay 2 u...

Страница 49: ...y Reversal Connection Using the MR 201 T Relay 2 Program the NAC circuit for non silence NAC circuit see Section 9 5 2 Intended for Connection to a Polarity Reversal Circuit of A Remote Station Receiving Unit Having Compatible Rating NOTE If you need to transmit supervisories or trouble conditions additional relay modules must be added Use relay 1 to transmit supervisory conditions Use the trouble...

Страница 50: ... station transmitter to the FCP 75 FACP dry contacts The FACP contacts must be supervised by the Remote Station Transmitter Module using end of line resistors ELRs with a value determined by the transmitter manufacturer Power is also provided by the Remote Station Transmitter Manufacturer Refer to the Remote Station Transmitter Manufac turer s Manual for details Figure 4 49 Transmitter Activated b...

Страница 51: ... of only one panel 5 1 2 Wiring Options to Connect Networked Panels 1 Fiber Optic Single Mode Use the FIK NIC and FIK FSL for up to 30dB loss of signal separation FIK FSL connects to the network using 9 125 micron single mode fiber 2 Fiber Optic Multi Mode Use the FIK NIC and FIK FM for up to 8dB loss of signal separation FIK FML connects to the network using 62 5 125 micron multi mode fiber 3 Twi...

Страница 52: ... types of fiber optic modules are used as one channel to transmit or receive communications with the FIK NIC ARCNET communication circuit The following describe the two types of fiber optic modules The FIK FML is a fiber module that allows the multi mode fiber to network between nodes The FIK FSL is a fiber module that allows the single mode fiber to network between nodes Each fiber loop module ca...

Страница 53: ...de the accessory cabinet Use the following steps to properly mount the FIK NIC KIT 1 Place the FIK NIC on the mounting bracket 2 Use the 6 pin cable included with FIK NIC to connect the FCP 75 to the FIK NIC The 6 pin cable must be run in conduit See Figure 5 50 Figure 5 54 Panel to FIK NIC Connection 3 Each FIK NIC has the ability to monitor for earth ground faults on the twisted pairs connected ...

Страница 54: ...NIC using a class B or class A wiring method A combination of both medium types can be used See Figure 5 55 Figure 5 56 Figure 5 57 and Figure 5 58 for FIK NIC wiring examples Unshielded Twisted Pair Wiring between Multiple Panels Unshielded twisted pair wiring between multiple panels is shown in Figure 5 55 Class A wiring is shown with a dotted line Figure 5 55 Twisted Pair Wiring Configuration C...

Страница 55: ... FCP 75 Manual P N LS10147 003FK E A 3 17 2021 55 Fiber Optic Multi Mode Wiring between Multiple Panels Fiber optic cable between multiple panels is shown in Figure 5 56 Class A is shown with a dotted line Figure 5 56 Fiber Optic Wiring Example Class A wiring ...

Страница 56: ...56 FCP 75 Manual P N LS10147 003FK E A 3 17 2021 Networking Common Communicator List FIK NIC Wiring Options Figure 5 57 Fiber Optic Wiring Single Mode Example Class A wiring ...

Страница 57: ...17 2021 57 Fiber Optic and Twisted Pair Wiring between Multiple Panels A mixture of fiber optic cable and twisted pair wiring between multiple panels is shown in Figure 5 58 Class A cabling is shown with dotted line Figure 5 58 Twisted Pair and Fiber Optic Combination Wiring Example Class A wiring ...

Страница 58: ...l ID for each Panel Network The network ID for each panel is set using DIP switch positions 1 through 5 See Figure 5 59 below for possible DIP switch settings Figure 5 59 Network ID Settings NOTE It is important that much thought is given when choosing the network IDs for each panel It is difficult to change the IDs once panel programming has begun ...

Страница 59: ...Select 6 for Network Programming 3 Press 1 to enter the Learn Network Menu 4 Press ENTER to add or remove panels connected to the network as member or guest 6 2 2 Edit Network Names The Edit Network Menu allows you to edit the panel name and edit the panels site name To Edit Panel Names 1 Enter the Installer Code The panel will automatically go to the Main Menu 2 Select 6 for Network Programming 3...

Страница 60: ... that dictates what functions the Fire Fighter Key has access to Because this is the profile for a key the user name and the Access Code can not be edited for this profile Profile 2 is the profile for the installer and is referred to as the Installer Code This profile s user name and panel functions can not be edited Table 6 1 lists the panel functions that can be selected for each user profile Fu...

Страница 61: ...l solution for reducing the number of paths required for reporting purposes A communicator is specified by panel number The network communicators will be used to report events according to the communicator report table Communicator Miscellaneous When using the SIA reporting format the communicator sends information according to the SIA Reporting Type The selections for this option are 1 pi modifie...

Страница 62: ...tion of network options fail the system will report a trouble of network options out of sync Use this Menu to redistribute changed options to the rest of the network The user will be required to choose a panel to source the options from Scroll down through the informational message and press ENTER to view the Select Source screen 1 Enter the Installer Code The panel will automatically go to the Ma...

Страница 63: ... Profile 01 20 Edit Name Profile 1 is the profile that dictates what functions the Firefighter Key has access to Because this is the profile for a keys the user name and the Access Code can not be edited for this profile Profile 2 is the profile for the installer and is referred to as the Installer Code This profile s user name and panel functions can not be edited See Section 6 2 5 Edit Access Co...

Страница 64: ...F2 Function Key F3 Function Key F4 Function Key Send Receive Firmware Updates Communicator Assignments Select Panel Primary 0 unused See Section 6 2 6 Communicator Miscellaneous SIA Options Enable pi SIA Modifier See Section Communicator Miscellaneous Include Panel ID in SIA Reporting Receiver Configuration Select Panel Select Receiver Receiver Number See Receiver Configuration Receiver Format Con...

Страница 65: ...ROL PANEL WHILE INSTALLING OR SERVICING Part Numbers Model Name Description Install Sheet PN FIK 2351 Photoelectric smoke detector I56 6632 FIK 2351T Photoelectric smoke detector with thermal 135 F I56 6633 FIK 2351R Photoelectric replacement smoke detector with remote test capability in DNR I56 6634 DNR DNRW Duct smoke detector housing Non relay photo sold separately I56 3051 FIK 5351 Fixed tempe...

Страница 66: ... for out back tap and T Tap Figure 7 1 Calculating wire run length for a simple out and back When you use T taps the total length of all taps and the main bus must be met in addition to the maximum distance requirements for the var ious wire gauges Wire Requirements Distance in Feet meters Wire Type RECOMMENDED Twisted unshielded pair 12 to 18 AWG 3 31mm2 to 0 82 mm2 50 ohms maximum per length of ...

Страница 67: ...ngth for a T tap 7 4 3 Wiring SLC in Class A Configuration Figure 7 3 illustrates how to wire the SLC loop for Class A installations Figure 7 3 Class A SLC Configuration NOTE 1 Style 6 does not use short circuit isolator devices NOTE 2 Style 7 requires an isolator module as the first device on the in and the out loop NOTE 3 No t taps allowed on class A SLC loops ...

Страница 68: ... the FIK W WGI For more information regarding gateway wiring instructions see SWIFT manual LS10036 000FK E 7 6 1 SLC Connections The FIK W WGI Wireless Gateway acts as a bridge between a group of wireless fire devices and a SLC loop on the FCP 75 It is powered by the SLC loops or by a regulated external 24 VDC UL listed power supply For details about wireless devices system setup and opera tion se...

Страница 69: ...r does not need to edit device type for detectors Any contact monitor modules on the system will be assigned type Manual Pull The installer will need to manually change the switch type if manual pull is not correct JumpStart Autoprogramming creates one zone Zone 1 and assigns all input points to Zone 1 Zone 1 is mapped to Output Group 1 8 1 2 Output Points JumpStart Autoprogramming creates three O...

Страница 70: ...nization detector on the system will display Select 1 for DUCT and 2 for NonDUCT 5 Press up arrow to select the next detector Select 1 for DUCT and 2 for NonDUCT Continue until all duct detectors have been selected Note You can move backwards through the list with down arrow 6 When you reach the last detector on this device press left arrow 7 The system will ask you if there are any duct detectors...

Страница 71: ...Mapping Overview Programming Overview FCP 75 Manual P N LS10147 003FK E A 3 17 2021 71 Figure 8 2 Input Point Assignment Example ...

Страница 72: ... specific Output Patterns Mapping examples are shown in Figure 8 4 Figure 8 5 Figure 8 6 System Zone Panel Site Fire Manual Pull Alarm System Aux 1 Alarm Fire Drill Water Flow Alarm System Aux 2 Alarm General Fire Alarm Detector Alarm heat or smoke detectors General Fire Supervisory Zone Aux 1 Alarm General Fire Pre Alarm Zone Aux 2 Alarm Interlock Alert Interlock Release Pre Alarm Fire Supervisor...

Страница 73: ...Mapping Overview Programming Overview FCP 75 Manual P N LS10147 003FK E A 3 17 2021 73 Figure 8 4 Example of Zone Events Mapped to Output Groups and Patterns ...

Страница 74: ...put Groups and Patterns Zone 4 Storage Floor 4 Zone 3 Offices Floor 3 Zone 4 Storage Floor 4 Zone 3 Offices Floor 3 Zone 1 Show Room Floor 1 Zone 4 Storage Floor 4 Zone 2 Show Room Floor 2 Zone 1 Show Room Floor 1 Zone 2 Show Room Floor 2 Zone 1 Show Room Floor 1 Zone 3 Offices Floor 3 Zone 2 Show Room Floor 2 Zone 1 Show Room Floor 1 ...

Страница 75: ...ou easily program the control panel using a Windows based computer HFSS is needed for Mapping When using HFSS you can set up the programming options for the panel save the options in a file then download the file to the panel You can connect to the control panel directly using the onboard USB or Ethernet Updates are available at www fike com 8 4 Programming Using an Annunciator You can program the...

Страница 76: ...t No any changes you have made since you entered the Program Menu will have no effect 8 4 2 Moving through the Menus Figure 8 7 shows how to move through Menu screens using the System Tests screen as an example Figure 8 7 Moving through Program Menu 8 4 3 Selecting Options and Entering Data There are several ways to make programming selections using the control panel depending on which screen you ...

Страница 77: ... FIK RPS1000 Power Supply FIK 5496 NAC Expander FIK 5880 LED IO Module FIK 5865 LED Annun Module FIK NIC Network Interface Card Delete Module Select Module Section 9 2 3 View Module List Select Module Section 9 2 4 Zone Edit Zone Select Zone Edit Zone Name Section 9 3 1 Zone Properties Verification Type 1 Count 2 Count Alarm Ver PAS SNGL ILOCK DBL ILOCK Heat Temp Set 135 to 150 F 135 to 190 F Smok...

Страница 78: ...on 9 5 1 SWITCH 1 2 3 MANUAL PULL WATERFLOW LATCH NON LATCH FIRE SUPERVSY LATCH NON LATCH FIRE DRILL SILENCE RESET P A S ACK ZONE AUX1 LATCH NON LATCH ZONE AUX2 LATCH NON LATCH SYSTEM AUX1 LATCH NON LATCH SYSTEM AUX2 LATCH NON LATCH DETECTOR FIRE TAMPER LATCH NON LATCH MANUAL RELEASE INTERLOCK Menu Options Defaults Comments Table 8 3 Programming Quick Reference List Continued ...

Страница 79: ... 2 3 4 Same as SWITCH W RELAY 2 3 4 Same as Relay Select Sensor2 3 UNUSED DETECTOR PHOTO No Accessory SDR BAS RLY BAS I SdrBa Intelligent Sounder Base ION No Accessory SDR BAS RLY BAS I SdrBa Intelligent Sounder Base IDP Devices on Internal SLC Enter Point Select Sensor1 2 3 DETECTOR1 2 3 4 HEAT No Accessory Section 9 5 1 SDR BAS RLY BAS I SdrBa Intelligent Sounder Base PHOTO DUCT No Accessory DCT...

Страница 80: ... RLY BAS I SdrBA Intelligent Sounder Base CO ALARM FIRE SUPR No Accessory SDR BAS RLY BAS I SdrBA Intelligent Sounder Base CO SUPR FIRE ALARM No Accessory SDR BAS RLY BAS I SdrBA Intelligent Sounder Base CO SUPR FIRE SUPR No Accessory SDR BAS RLY BAS I SdrBA Intelligent Sounder Base W Detector1 2 4 Photo Acclimate1 2 3 5 Heat W SUP DET1 2 4 Same as W Detector Internal Power and External Power Poin...

Страница 81: ...E AUX2 SYSTEM AUX1 SYSTEM AUX2 WATERFLOW FIRE SUPER VISORY FIRE TAMPER FIRE DRILL SILENCE RESET P A S ACK ZONE AUX 1 ZONE AUX2 SYSTEM AUX1 SYSTEM AUX2 MANUAL RELEASE INTER LOCK STATUS POINT A SWITCH Same as B SWITCH B DETECT 2 WIRE SMOKE Zone Edit Name 4 WIRE SMOKE CO 4 WIRE DET CO 4 WIRE SUP DET Latch Non Latch A DETECT 2 WIRE SMOKE 4 WIRE SMOKE CO 4 WIRE DET CO 4 WIRE SUP DET Latch Non Latch Onl...

Страница 82: ...achine Bypass Y or N N Phone Line Unused Y or N N Edit Ethernet IP Address Subn Mask SubNet Default Gateway DHCP Enable AlarmNet Timers Ethernet Supervise 75 sec 90 Sec 3 min 5 min 1 hr 24 hrs 30 days None 5 Minutes Old Alarm Time 10 min 15 min 30 Minutes 1 hr 2 hrs 4 hrs 8 hrs 12 hrs 24hrs none 30 Minutes Phone Line Gains Dialing High High Low Normal Reporting Low Low Normal High Daytime Nighttim...

Страница 83: ... 250 seconds 60 sec Low AC Report Time 0 30 hours 3 hrs AC Freq 50 Hz 60Hz 60 Hz Internal Clock Display Format AM PM AM PM MIL Auto resound 4 hours 24 hours 24 hours Miscellaneous Options SYNC Strobes when Silenced Y N Section 9 6 5 N Auto Display Events Y N N Daylight Saving Options Auto Daylight Saving Time Y Y Section 9 6 6 N DST Start Select week 1st 2nd 3rd 4th or Last Select month DST End Ed...

Страница 84: ...cter for the modules name or press the right arrow to bypass the name edit Press the right arrow to move to the next character NOTE Before any customized programming is done JumpStart Autoprogramming should be run first After JumpStart is run thoroughly test the system The reason the system should be tested after JumpStart Autoprogramming is because JumpStart automatically programs the system sear...

Страница 85: ...eed to delete a module follow these steps You must be in the Main Menu to perform this task If necessary enter the Installer Code 1 Enter the Installer Code 2 Select 7 for Program Menu 3 Press 1 to enter Module Menu 4 Press 3 to delete a module 5 From the next screen select a module to delete A warning screen will display 6 If you want to proceed with deleting the module select Yes To cancel selec...

Страница 86: ...arm occurs immediately when a single device of any of the following types goes into alarm detector manual pull water flow Aux1 or Aux2 This is considered the most typical operation and is the default for all zones 2 Count When this type of alarm delay is used two or more detectors within the zone must go into alarm in order for the zone to report an alarm Switches of type manual pull Detector swit...

Страница 87: ...y If this option is enabled for a zone the zone will respond to an alarm condition as follows The zone will not go into alarm for 15 seconds to allow an on site operator to activate the acknowledge switch If the operator does not press the acknowledge switch within 15 seconds the zone will go into alarm If the operator presses the acknowledge switch within 15 seconds a 180 second time frame will b...

Страница 88: ...these steps 1 Enter the Installer Code 2 Select 7 for Program Menu 3 Press 3 to enter Group Menu 4 Press 1 to edit group 5 Enter the number of the group you wish to edit then press ENTER Edit Group Name 6 To edit the group name press 1 You can use words to display a descriptive name for a group Edit Group Properties 7 To edit the group properties Press 2 from the edit group Menu The Edit Group Men...

Страница 89: ...lenceable zone assignment input points detector accessory base options group assignment output points and point name 9 5 1 Point Programming For SLC To program for points follow these steps 1 Enter the Installer Code 2 Select 7 for Program Menu 3 Press 4 to enter point Menu 4 Press the up or down arrows to select the desired module refer to Section 8 5 Quick Reference Table for available choices 5...

Страница 90: ... is an alternative way of causing a fire drill It has the same operation as the fire drill option available from the annunciator When the switch is activated a fire drill begins when the switch is de activated a fire drill ends SILENCE System level switch provides an alternate way to silence the system same effect as pressing the Silence key RESET System level switch provides an alternate way to r...

Страница 91: ...ion type Use for driving standard notification appliances AUX CONST Use constant power for applications that require a constant auxiliary power source Power is always present at Constant circuits AUX RESET Use for auxiliary power resettable applications See Resettable Power on page 45 to learn how this option operates AUX DOOR Use for auxiliary power door holder applications For example if you wer...

Страница 92: ...ching feature only appears for waterflow supervisory tamper zone aux1 zone aux2 system aux1 and system aux2 WATERFLOW SUPERVSY TAMPER FIRE DRILL SILENCE RESET PAS_ACK ZN_AUX1 ZN_AUX2 SYS_AUX1 SYS_AUX2 MAN REL ILOCK STATUS POINT Non latching Used to activate an ancillary Output Group that does not active alarm sound PZT display status or report events Reset has no affect on this point A SWITCH Same...

Страница 93: ...p or down arrow key then press ENTER 7 Enter the minutes or press the up or down arrow key then press ENTER 8 Select AM or PM by pressing the up or down arrow key then press ENTER 9 Select Report Time Interval by pressing the up or down arrow key then press ENTER Time Interval selections are 24hr 12hr 6hr and 4 hr Phone Lines To access the phone lines screen 1 Enter the Installer Code 2 Select 7 f...

Страница 94: ...e up or down arrow then press ENTER Answering Machine Bypass This option is used in conjunction with the HFSS Programming Tool This feature ensures that an answering machine will not interfere with communication between the panel and the computer If an answering machine is used at the panel site enable this feature if an answering machine is not used disable the feature This option is factory prog...

Страница 95: ... 24 hours 1 hour Old Alarm 30 minutes 15 minutes 10 minutes none 24 hours 12 hours 6 hours 4 hours 2 hours 1 hour defaults Figure 9 9 AlarmNet Timers Phone Line Gains 1 Enter the Installer Code The panel will automatically go to the Main Menu 2 Select 7 for Panel Programming 3 Select 5 for System Options 4 From the next Menu select 1 for Communication Options 5 Select 5 for Phone Line Gains 6 The ...

Страница 96: ...days 1 9 2 holidays 10 18 Figure 9 12 Edit Holidays Screen 6 Enter the month of the Holiday then press ENTER 7 Enter the day of the month for the Holiday then press ENTER 8 Repeat steps 6 and 7 for any remaining holidays you wish to program 9 6 4 Time Options Through this programming option you can set the water flow delay time low AC report delay enable or disable automatic daylight savings time ...

Страница 97: ... calculate time from the internal crystal The internal crystal is not as accurate as the AC power source and 60 Hz should normally be selected The panel defaults to the 60 Hz selection To change the AC line frequency continue programming from steps above 9 Select 60 or Intl by pressing the up or down arrow then press ENTER Clock Display Format AM PM or Military To change the system clock display f...

Страница 98: ...Options The default values for the DST Start and End are DST Start The second Sunday in March DST End The first Sunday in November To set the start and end for Daylight Saving Time 6 Press the up or down arrow to select the week 1st 2nd etc Daylight Saving Time starts then press ENTER to make your selection and move to the month setting 7 Press the up or down arrow to select the month January Dece...

Страница 99: ...ion if you add more devices when you Jump Start again the additional devices are added but you do not lose any of your previous custom programming To run JumpStart Autoprogramming 1 Enter the Installer Code 2 Select 7 for Program Menu 3 Select 6 for JumpStart Autoprogramming 4 Press the up or down arrow to select Yes from the warning screen 5 Press ENTER 9 8 Restore Defaults This option allows you...

Страница 100: ...upervisories and troubles provides status information and prompts for input These messages can be up to 80 characters displaying over four lines of 20 characters each Annunciator keys beep when they are pressed 10 2 2 Banner The banner is the message that displays on the control panel when the system is in normal mode no alarm or trouble condition exists and Menus are not in use You can create a c...

Страница 101: ...o Enable Zone Points 2 Use the up or down arrow key to move through the list of zones Press ENTER to select the zone highlighted Disable Enable Point 1 Press 7 to Disable Enable Point 2 Choose Module 3 Use the up or down arrow key to choose Point and press ENTER 4 Press the right arrow to disable or enable Point Inhibit Output Group Inhibiting an Output Group prevents the group from being used by ...

Страница 102: ... You can press any key to end manually while the test is still in progress When the test ends you will be returned to the Test Menu 10 4 6 Conduct a Walk Test Walk Test is a feature which allows one person to test the fire alarm system The Walk Test will run for 4 hours or until the user manually exits If an alarm or pre alarm condition is occurring in the system you will not be able to enter the ...

Страница 103: ...user to Reset the Communicator The LCD will display Communicator Reset in progress Please Wait You will be returned to the Main Menu when the reset is complete The communicator is not allowed to be reset when alarms or supervisories are active Communicator reset is not allowed if any of the follow ing are active Fire Alarm Fire Supervisory Fire Pre Alarm CO Alarm CO Supervisory 10 4 11 Check Detec...

Страница 104: ...d date Press the left arrow key to return About Panel Press 1 to access About Panel to view the panel model serial number and system version number and date Send Receive firmware updates The FCP 75 has the ability to be updated in the field The latest FCP 75 Firmware Update Utility can be downloaded from the Fike web site Once a panel has been updated using the Firmware Update Utility you can use ...

Страница 105: ... Table 10 1 describes the behavior of the panel in each of these modes When looking at the LCD the screen will display FIRE for the Fire System CO for the CO System The highest priority event will dis play first and include the event count see Figure 10 6 Press the down arrow to view the location and type of alarm supervisory or trouble If the panel is programmed to Auto Display Event information ...

Страница 106: ...r the appropriate code or rotate the key to activate the Main Menu Alarm A smoke detector goes into alarm or a pull station is activated CO detector goes into alarm If more than 3 categories are active at a single time screen will display as shown The communicator seizes control of the phone line and calls the central station The on board annunciator sounds a loud steady beep any notification devi...

Страница 107: ...ey to silence the annunciator Once the supervisory condition has been corrected the system will restore itself automatically Trouble A system troublecondition occurs A trouble condition with a CO detector The communicator seizes control of the phone line and calls the central station The on board annunciator sounds a loud pulsing beep in the sequence one second on nine seconds off SYSTEM TROUBLE L...

Страница 108: ...erlock switch input in the system and the Single Interlock does not An interlock switch is typically a dry contact pressure switch Prealarm A single detector trips in a 2 Count zone 2 Count means two detectors must trip before an alarm is reported Touchpad PZT beeps The LCD displays a screen similar to this one Press down arrow to view the prealarm A screen similar to this one displays All system ...

Страница 109: ...tector is activated the Pre Alert output will activate and the Pre Alarm output will deactivate This alerts the user that the initial stages required for a release condition are present Also refer to Table 10 4 Conditions required for an General Alarm and Release Output Activation If two or more addressable detectors or a manual release switch activate the Alarm and the Release outputs will activa...

Страница 110: ...d either a manual release switch or 2 activated addressable detectors When these conditions are met the Release and General Alarm outputs will activate and the Alert output will deactivate 10 8 Smoke Alarm Verification Figure 10 2 illustrates how the Smoke Alarm Verification cycle operates Figure 10 2 Smoke Verification Cycle During the Confirmation Period if there is no alarm indication then the ...

Страница 111: ...select the End F KEY Recording option 5 The panel will return to the Idle screen 10 9 2 Aborting an F Key Macro Recording Session 1 After an F Key macro recording session has been started the session can be canceled at any time by accessing the F Key Recording Menu and selecting Abort F KEY Recording option 2 The panel will return to the Idle screen 10 9 3 Erasing an F Key Macro 1 If an F Key macr...

Страница 112: ...0 Receiver 001 Auto dialer test communications trouble line 1 restore YK 1 YKNN000001 3 350 Receiver 001 Auto dialer test communications trouble line 2 YC 2 YCNN000002 1 350 Receiver 002 Auto dialer test communications trouble line 2 restore YK 2 YKNN000002 3 350 Receiver 002 Automatic test normal RP 0 RPNN000000 1 602 00 000 Automatic test off normal RY 0 RYNN000000 1 608 00 000 Battery voltage t...

Страница 113: ...Point SRNNXXPPPP 3 203 Exp ID Point Remote programming aborted or ended with errors RU 0 RUNN000000 1 413 00 000 Remote programming ended normally RS 0 RSNN000000 1 412 00 000 Repeater ground fault trouble EM 0103 EMNN000103 1 334 Panel ID 103 Repeater ground fault trouble restore EN 0103 ENNN000103 3 334 Panel ID 103 Repeater missing trouble EM 0100 EMNN000100 1 334 Panel ID 100 Repeater missing ...

Страница 114: ...er Alarm QS 0 QSNN000000 1 241 00 000 ECS Supervisory Tamper Alarm Restore QR 0 QRNN000000 3 241 00 000 ECS Output Group Trouble QT Group 1000 QTNN001GGG 1 320 00 Group ECS Output Group Trouble Restore QJ Group 1000 QJNN001GGG 3 320 00 Group External Reset Silence Fire Drill switch trou ble UT 0000 UTNN000000 1 373 00 000 External Reset Silence Fire Drill switch trou ble restore UJ 0000 UJNN000000...

Страница 115: ...171 00 000 Voice Aux ECS 1 Alarm Restore UH 3 UHNN003000 3 171 00 000 Voice Aux ECS 2 Alarm UA 4 UANN004000 1 172 00 000 Voice Aux ECS 2 Alarm Restore UH 4 UHNN004000 3 172 00 000 Voice Aux ECS 3 Alarm UA 5 UANN005000 1 173 00 000 Voice Aux ECS 3 Alarm Restore UH 5 UHNN005000 3 173 00 000 Voice Aux ECS 4 Alarm UA 6 UANN006000 1 174 00 000 Voice Aux ECS 4 Alarm Restore UH 6 UHNN006000 3 174 00 000 ...

Страница 116: ... 373 Exp ID Point Detector Trouble restore pi Exp ID FJ Point FJNNXXPPPP 3 373 Exp ID Point Detector CO Alarm pi Exp ID GA Point GANNXXPPPP 1 162 Exp ID Point Detector CO Alarm Restore pi Exp ID GH Point GHNNXXPPPP 3 162 Exp ID Point Detector CO Supervisory Alarm pi Exp ID GS Point GSNNXXPPPP 1 200 Exp ID Point Detector CO Supervisory Alarm Restore pi Exp ID GR Point GRNNXXPPPP 3 200 Exp ID Point ...

Страница 117: ...ated ECS Alarm pi Exp ID QA 0 QANNXX0000 1 220 Exp ID 000 LOC Mic Activated ECS Alarm Restore pi Exp ID QH 0 QHNNXX0000 3 220 Exp ID 000 LOC ECS Alarm pi Exp ID QA Emergency QANNXXE000 1 220 Emer gency Exp ID 000 LOC ECS Alarm Restore pi Exp ID QH Emergency QHNNXXE000 3 220 Emer gency Exp ID 000 Manual pull switch alarm pi Exp ID FA Point FANNXXPPPP 1 115 Exp ID Point Manual pull switch alarm rest...

Страница 118: ...based AUX1 switch trouble pi Exp ID UT Point UTNNXXPPPP 1 373 Exp ID Point System based AUX1 switch trouble restore pi Exp ID UJ Point UJNNXXPPPP 3 373 Exp ID Point System based AUX2 switch alarm pi Exp ID UA Point UANNXXPPPP 1 140 Exp ID Point System based AUX2 switch alarm restore pi Exp ID UH Point UHNNXXPPPP 3 140 Exp ID Point System based AUX2 switch disabled pi Exp ID UB Point UBNNXXPPPP 1 5...

Страница 119: ... Point SJNNXXPPPP 3 373 Exp ID Point Zone based AUX1 switch alarm pi Exp ID UA Point UANNXXPPPP 1 140 Exp ID Point Zone based AUX1 switch alarm restore pi Exp ID UH Point UHNNXXPPPP 3 140 Exp ID Point Zone based AUX1 switch disabled pi Exp ID UB Point UBNNXXPPPP 1 571 Exp ID Point Zone based AUX1 switch enabled pi Exp ID UU Point UUNNXXPPPP 3 571 Exp ID Point Zone based AUX1 switch trouble pi Exp ...

Страница 120: ... a EE ZZ FA15 Fire Alarm Zone Zone n a n a 05 n a EE Z FA5 Fire Alarm Point Point n a 01 n a 123 EE ZZ EE ZZZ pi01 FA123 Fire Alarm Point Point n a 33 n a 203 EE ZZ EE ZZZ pi11 FA203 Expander Trouble n a n a 11 n a n a EE ZZ ET11 Auto Test n a n a n a n a n a EE Z RP0 Battery Trouble Panel 32 n a n a 98 n a n a EE ZZ YT98 Battery Trouble Expander 18 n a n a 18 n a n a EE ZZ YT18 SLC Loop Shorted n...

Страница 121: ...orted n a 01 44 n a n a EE PP MM ZZZZ ET01440000 Program Begin n a 32 n a n a n a EE PP MM ZZZZ LB32000000 Program Begin n a 22 n a n a n a EE PP MM ZZZZ LB22000000 AC Power Loss Panel 22 n a 22 98 n a n a EE PP MM ZZZZ AT22980000MM 00 Fire Trouble Point 22 97 n a 200 EE PP MM ZZZZ FT22970200 Fire Trouble Zone 22 97 1 n a EE PP MM ZZZZ FT22970001MM 00 Fire Trouble NAC Point 22 98 n a NAC Circuit 7...

Страница 122: ...ing recognized trouble message Missing displays Check hardware connections If devices are physically connected make sure wiring is correct see Section 7 4 For the main panel the positive side of device must be connected to terminal 34 the negative side must be connected to Terminal 33 For SLC devices make sure the device connects to the SLC loop via the SLC OUT terminals Make sure SLC devices have...

Страница 123: ...en the system will cease normal operation leaving the premise unprotected 4 Select the SLC loop 5 Enter the SLC address of the device you wish to locate The LED on the selected device will start flashing 6 Press left arrow to exit SLC device locater function 12 2 2 SLC Multi Locater This feature is the same as SLC Device Locater except you can locate up to 8 devices on a single search Follow these...

Страница 124: ...er or press the up or down arrow to select the point you wish to test then press ENTER 5 Press ENTER to generate an alarm for an input point or activate an output point 6 To exit press the left arrow key 12 3 Earth Fault Resistance Table 12 2 lists the earth fault resistance detection for each applicable terminal on the FACP NOTE Once you exit the system will resume normal operation TERMINAL LOW B...

Страница 125: ...d 7 Onboard 45 Onboard 8 Onboard 46 Onboard 9 Onboard 47 Onboard 10 Onboard 48 Onboard 11 Onboard 49 Onboard 12 Onboard 50 Onboard 13 Onboard 52 Onboard 14 Onboard 53 Onboard 15 Onboard 54 Onboard 16 Onboard 55 Onboard 17 Onboard 56 Onboard 18 Onboard 57 Onboard 19 Onboard 58 Onboard 20 Onboard 59 Onboard 21 Onboard 60 Onboard 22 Onboard 61 Onboard 23 Onboard 62 Onboard 24 Onboard 63 Onboard 25 On...

Страница 126: ...anual P N LS10147 003FK E A 3 17 2021 Installation Records IDP SLC Device Point Record Detector Addr Zone Group Description Detector Addr Zone Group Description Table 13 3 IDP Detector Installation Record Continued ...

Страница 127: ...with this feature This control is UL listed for panel wide Synchronization Manufacturer Model Audio Visual Type AMSECO SH24W 153075 x x Horn Strobe SAD24 153075 x Strobe SAD24 75110 x Strobe SL24W 75110 x Strobe SL24C 3075110 x Strobe SLB24 75 x Strobe RSD24 153075 x Strobe RSD24 75110 x Strobe SH24W 75110 x x Horn Strobe SH24W 3075110 x x Horn Strobe SHB24 75 x x Horn Strobe SCM24W 153075 x Chime...

Страница 128: ...Strobe P2430 FC x x Horn Strobe P2430W FC x x Horn Strobe P2430K FC x x Horn Strobe P2475 FC x x Horn Strobe P2475W FC x x Horn Strobe P2475K FC x x Horn Strobe P24110 FC x x Horn Strobe P24110W FC x x Horn Strobe P24110K FC x x Horn Strobe S2430W FC x Strobe S2430K FC x Strobe S2475 FC x Strobe S2475W FC x Strobe S2475K FC x Strobe S24110 FC x Strobe S24110W FC x Strobe S24110K FC x Strobe Federa...

Страница 129: ...ulti Candella Horn Strobe Ceiling Mount GCCR24 x Multi Candella Horn Strobe Ceiling Mount GCS24 x Multi Candella Strobe Ceiling Mount GCSR24 x Multi Candella Strobe Ceiling Mount GECR 24 x x Multi Candella Horn Strobe GES24 15 x Strobe GES24 30 x Strobe GES24 60 x Strobe GES24 75 x Strobe GES24 110 x Strobe GES24 15 75 x Strobe GES24 177 x Strobe GES3 24 x Multi Candella Strobe GESR 24 x Multi Can...

Страница 130: ...P x x 2 Wire Horn Strobe P2RH x x 2 Wire Horn Strobe High Candela P2RH P x x 2 Wire Horn Strobe High Candela PC2RH x x 2 Wire Horn Strobe High Candela PC2RH P x x 2 Wire Horn Strobe High Candela P2W x x 2 Wire Horn Strobe P2W P x x 2 Wire Horn Strobe PC2W x x 2 Wire Horn Strobe PC2W P x x 2 Wire Horn Strobe P2WH x x 2 Wire Horn Strobe High Candela P2WH P x x 2 Wire Horn Strobe High Candela PC2WH x...

Страница 131: ...4X4 PC4RL x x Horn Strobe 4W Red Ceil 4X4 PC4WL x x Horn Strobe 4W WHT Ceil 4X4 SR x Strobe SR P x Strobe SCR x Strobe SCR P x Strobe SRH x Strobe High Candela SRH P x Strobe High Candela SCRH x Strobe High Candela SCRH P x Strobe High Candela SW x Strobe SW P x Strobe SCW x Strobe SCW P x Strobe SWH x Strobe High Candela SWH P x Strobe High Candela SCWH x Strobe High Candela SCWH P x Strobe High ...

Страница 132: ...atherproof AH 24WP x Horn Weatherproof AMT 241575W x x Multi Tone Horn Strobe AMT 24MCW x Mutli Tone Horn Strobe AMT 241575W NYC x x Multi Tone Horn Strobe AMT 12 24 x Multi tone Horn AMT 12 24 NYC x Multi tone Horn AS 121575W x Horn Strobe NH 12 24 x x Horn AS 241575W x x Horn Strobe AS 24MCC x x Horn Strobe AS 24MCCH x x Horn Strobe AS 24MCW x x Horn Strobe AS 24MCWH x x Horn Strobe ASWP 2475W x...

Страница 133: ...Strobe MTWPB 2475W x x Multitone Horn Strobe MTWPG 2475W x x Multitone Horn Strobe MTWPR 2475W x x Multitone Horn Strobe MTWPA 24MCCH x x Multitone Horn Strobe ZNH x Horn NS 121575W x x Horn Strobe NS 241575W x x Horn Strobe NS 24MCW x x Horn Strobe NS 24MCC x x Horn Strobe NS 24MCCH x x Horn Strobe ZNS MCW x x Horn Strobe ZNS MCWH x x Horn Strobe ZNS 24MCC x x Horn Strobe ZNS 24MCCH x x Horn Stro...

Страница 134: ...ZRS 24MCC x Strobe ZRS 24MCCH x Strobe MB G6 24 x Motor Bell MB G10 24 x Motor Bell MB G6 12 x Motor Bell MB G10 12 x Motor Bell MIZ 24 R x Mini Horn MT 12 24 R x x Multitone Horn MT4 12 2z x x Multitone Horn ZRS MCW x Strobe MTWPR 24MCCH x x Multitone Horn Strobe NH 12 24R x Horn HSR x Horn Strobe HSW x Horn Strobe STR x Strobe STW x Strobe HNR x Horn HNW x Horn FCP 75 Identifier 24H Operating Vo...

Страница 135: ...40 loop 611UT 601U or 602U S10 S00 S03 40 loop 612U 601U or 602U S10 S00 S03 40 loop 612UD 601U or 602U S10 S00 S03 40 loop 711U 701E or 701U N A S10A 25 loop 712U 701E or 701U N A S10A 25 loop 713 5U 702E or 701U N A S10A 25 loop 713 6U 702E or 701U N A S10A 25 loop 721 U S10A N A S10A 30 loop 721 UT S10A N A S10A 30 loop Falcon 525 FDT1 N A 17 loop 525T FDT1 N A 17 loop Hochiki SIH 24F HS 224D o...

Страница 136: ...toelectric 0 50 60 70 System Sensor 2112 24AITR Photoelectric 0 50 60 70 System Sensor 2112 24 D Photoelectric 0 05 50 System Sensor 2112 24R Photoelectric 0 50 60 70 System Sensor 2112 24TR Photoelectric 0 50 60 70 System Sensor 2112 24T D Photoelectric w 135 Thermal 0 05 50 System Sensor 2112 24TSRB Photoelectric w 135 Thermal Supervisory Relay 15 45 System Sensor 2312 24TB Photoelectric 0 12 50...

Страница 137: ...e Detector Base Detector Type Max Standby Current mA Alarm Current mA Table A 3 Compatible Four Wire Smoke Detectors Manufacturer Model Type Current mA Edwards DH150A Floor Mount 96 Edwards DH154A Flush Mount 96 Edwards DH158A Surface Mount 96 Rixon Firemark FM 980 Floor Mount single 68 Rixon Firemark FM 996 Surface Wiring 68 Rixon Firemark FM 998 Concealed Wiring 68 Table A 4 Compatible Door Hold...

Страница 138: ... Lens ALERT White SPSW CLR ALERT Wall High Fidelity Speaker Strobe Clear Lens ALERT White SPSW P Wall High Fidelity Speaker Strobe Plain Red SPSWH Wall High Fidelity Speaker Strobe High Candela White SPSWH P Wall High Fidelity Speaker Strobe High Candela Plain Red SPRL Wall High Fidelity Speaker Red SPWL Wall High Fidelity Speaker White SPCRL Ceiling High Fidelity Speaker Red SPCWL Ceiling High Fi...

Страница 139: ...ss enter to accept B 2 Example Name Edit 1 Press the up or down arrow to select upper case letters mode Press 2 until F appears 2 Press the up or down arrow to change mode to lower case letters Press 3 until i appears 3 Press 6 until r appears 4 Press 2 until e appears 5 Press 0 to space then continue to next word using the same process 6 Press ENTER to accept Figure B 1 Edit Name Example Lower Ca...

Страница 140: ...bers 1 1 2 3 4 2 5 6 7 8 3 9 10 11 12 4 13 14 15 16 5 17 18 19 20 6 21 22 23 24 7 25 26 27 28 8 29 30 31 32 9 33 34 35 36 10 37 38 39 40 11 41 42 43 44 12 45 46 47 48 13 49 50 51 52 14 53 54 55 56 15 57 58 59 60 16 61 62 63 64 17 65 66 67 68 18 69 70 71 72 19 73 74 75 76 20 77 78 79 80 21 81 82 83 84 22 85 86 87 88 23 89 90 91 92 24 93 94 95 96 25 97 98 99 100 26 101 102 103 104 27 105 106 107 108...

Страница 141: ...FCP 75 Manual P N LS10147 003FK E A 3 17 2021 141 Appendix D Cadence Patterns The cadence patterns shown below are available for use with the control panel Figure D 1 Cadence Patterns ...

Страница 142: ...unique password Securely configure networks and firewalls Assess security risks Develop a Disaster and Recovery Plan Develop a Backup and Recovery Strategy Install configure and keep anti virus software updated on all computers which access the panel Keep operating system updated on all computers which access the panel Deliver all required system information upon delivery to the system owner Train...

Страница 143: ...module where the point you want to view is located 4 The fourth line of the display shows the sensitivity status NORMAL means the detector is in compliance with NFPA 72 CAL MAINT means the detector is in compliance with NFPA 72 but maintenance should be performed soon CAL TRBLE means the detector is not in compliance with NFPA 72 Set Time and Date 1 Press ENTER to access Main Menu then enter a cod...

Страница 144: ...Cut along dotted line ...

Страница 145: ...FCP 75 Manual P N LS10147 003FK E A 3 17 2021 145 ...

Страница 146: ...FIKE CORPORATION 704 SW 10th Street Blue Springs MO 64015 Telephone 1 816 229 3405 www fike com ...

Отзывы: