FCP-75 Manual —
P/N:LS10147-003FK-E:A 3/17/2021
39
FIK-5880 LED Driver Module
Control Panel Installation
On connector P1, Pin 12 is a programmable Open Collector Output for controlling a PZT. If used, the FIK-5880 PZT will match the PZT pat-
tern of the on-board or remote annunciator.
Figure 4.33 FIK-5880 Board Layout
4.9.4 Dry Contact Wiring
The 8 input circuits on the FIK-5880 board are for monitoring switch inputs-any type of switch supported by the control panel can be used
with the FIK-5880. For example, you can use a FIK-5880 to monitor pull stations, water flow, tamper, reset, or silence switches.
NOTE:
The circuit connected to “Open Collector Output” (last pin on P1) must be current-limited so that no more than 100 mA of current is
allowed to flow into the Open Collector Transistor.