Receivers Compatible with the Control Panel
Reporting
FCP-75 Manual —
P/N:LS10147-003FK-E:A 3/17/2021
117
ECS Control Circuit Trouble
pi Exp. ID QT
Point #
QTNNXXPPPP
1
320
Exp. ID
Point #
ECS Control Circuit Trouble Restored
pi Exp. ID QJ
Point #
QJNNXXPPPP
3
320
Exp. ID
Point #
ECS Relay Trouble
pi Exp. ID QT
Point #
QTNNXXPPPP
1
320
Exp. ID
Point #
ECS Relay Trouble Restored
pi Exp. ID QJ
Point #
QJNNXXPPPP
3
320
Exp. ID
Point #
ECS Notification Trouble
pi Exp. ID QT
Point #
QTNNXXPPPP
1
320
Exp. ID
Point #
ECS Notification Trouble Restored
pi Exp. ID QJ
Point #
QJNNXXPPPP
3
320
Exp. ID
Point #
External Reset/Silence/Fire Drill switch dis-
abled
pi Exp. ID UB
Point #
UBNNXXPPPP
1
571
Exp. ID
Point #
External Reset/Silence/Fire Drill switch en-
abled
pi Exp. ID UU
Point #
UUNNXXPPPP
3
571
Exp. ID
Point #
External Reset/Silence/Fire Drill switch trou-
ble
pi Exp. ID UT
Point #
UTNNXXPPPP
1
373
Exp. ID
Point #
External Reset/Silence/Fire Drill switch trou-
ble restore
pi Exp. ID UJ
Point #
UJNNXXPPPP
3
373
Exp. ID
Point #
Interlock switch alarm (Water Release Zone) pi Exp. ID FA
Point #
FANNXXPPPP
1
110
Exp. ID
Point #
Interlock switch alarm restore (Water Release
Zone)
pi Exp. ID FH
Point #
FHNNXXPPPP
3
110
Exp. ID
Point #
Interlock switch disabled
pi Exp. ID FB
Point #
FBNNXXPPPP
1
571
Exp. ID
Point #
Interlock switch enabled
pi Exp. ID FU
Point #
FUNNXXPPPP
3
571
Exp. ID
Point #
Interlock switch trouble (Water Release
Zone)
pi Exp. ID FT
Point #
FTNNXXPPPP
1
373
Exp. ID
Point #
Interlock switch trouble restore (Water Re-
lease Zone)
pi Exp. ID FJ
Point #
FJNNXXPPPP
3
373
Exp. ID
Point #
LOC Mic Activated ECS Alarm
pi Exp. ID QA
0
QANNXX0000
1
220
Exp. ID
000
LOC Mic Activated ECS Alarm Restore
pi Exp. ID QH
0
QHNNXX0000
3
220
Exp. ID
000
LOC ECS # Alarm
pi Exp. ID QA
Emergency #
QANNXXE000
1
220 +
Emer-
gency #
Exp. ID
000
LOC ECS # Alarm Restore
pi Exp. ID QH
Emergency #
QHNNXXE000
3
220 +
Emer-
gency #
Exp. ID
000
Manual pull switch alarm
pi Exp. ID FA
Point #
FANNXXPPPP
1
115
Exp. ID
Point #
Manual pull switch alarm restore
pi Exp. ID FH
Point #
FHNNXXPPPP
3
115
Exp. ID
Point #
Manual pull switch disabled
pi Exp. ID FB
Point #
FBNNXXPPPP
1
571
Exp. ID
Point #
Manual pull switch enabled
pi Exp. ID FU
Point #
FUNNXXPPPP
3
571
Exp. ID
Point #
Manual pull switch trouble
pi Exp. ID FT
Point #
FTNNXXPPPP
1
373
Exp. ID
Point #
Manual pull switch trouble restore
pi Exp. ID FJ
Point #
FJNNXXPPPP
3
373
Exp. ID
Point #
Manual release switch alarm
(Water Release Zone)
pi Exp. ID FA
Point #
FANNXXPPPP
1
110
Exp. ID
Point #
Manual release switch alarm restore (Water
Release Zone)
pi Exp. ID FH
Point #
FHNNXXPPPP
3
110
Exp. ID
Point #
Manual release switch disabled
pi Exp. ID FB
Point #
FBNNXXPPPP
1
571
Exp. ID
Point #
Manual release switch enabled
pi Exp. ID FU
Point #
FUNNXXPPPP
3
571
Exp. ID
Point #
Manual release switch trouble
(Water Release Zone)
pi Exp. ID FT
Point #
FTNNXXPPPP
1
373
Exp. ID
Point #
Manual release switch trouble restore (Water
Release Zone)
pi Exp. ID FJ
Point #
FJNNXXPPPP
3
373
Exp. ID
Point #
Notification output point disabled
pi Exp. ID FB
Point #
FBNNXXPPPP
1
571
Exp. ID
Point #
SIA Reporting Format
Contact ID Reporting Format
SIA pi Modifier
SIA
Event Description
Module ID
# (If Any)
SIA
Event
Codes
Parameter
Fixed Length
Format NN - panel
ID
XX- SBUS ID
ZZZ- Zone #
PPPP- Point #
GGG- Group #
E- Emergency #
RRRR-Receiver #
Qualifier
Event
Code
Group #
Contact #
Table 11.2 Reporting Formats Table (Continued)