4.0 CONFIGURATION MENU
CyberCat 254/1016 Programming Manual
4-27
P/N: 06-539
Rev 3, 08/2013
4.3.5.2 HOW TO ASSIGN EVACUATION SETS TO A ZONE
The Evacuation Sets screen allows you to set which zones will broadcast the Evacuation or Alert message in
response to the selected zone entering the Alarm State. Each zone can activate any combination of other
zones for Evacuation or Alert.
From the “Zone” screen, press the F2 key to access the “Evacuation Sets” screen, as shown below:
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A
Z O N E : 0 0 1
A L A R M
S E T S
B
V O I C E
@
Z O N E : 0 0 1 - 0 2 0
C
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
D
E A - - - - - - - - - - - - - - - - - -
Exhibit 4-41: Evacuation Sets Screen
•
Row A (ZONE:) - This field allows you to select the zone number to assign an alarm set to. Use the
◄►
arrow keys to position the cursor under the field; then use the +/- keys to change zone number.
•
Row B – This field allows you to set the 20 zone range that is displayed in Rows C & D. Use the
◄►
arrow keys to position the cursor under the field; then use the +/- keys to increment/decrement
the group of 20 forward or backwards (Zones 001-254).
•
Row C – These numbers act as placeholders and zone number indicators for the range of zones
selected on Row B.
•
Row D - This range of fields allows you to select what condition this zone activates when the zone
displayed in Row A goes into Alarm.
-
= not programmed for this zone
E
= initiates Evacuation condition
A
= initiates Alert condition
Use the
◄►
arrow keys to position the cursor under the specific zone position; then use the
+/-
keys
to toggle the status.