4.0 CONFIGURATION MENU
CyberCat 254/1016 Programming Manual
4-23
P/N: 06-539
Rev 3, 08/2013
B. CyberCat 1016
From the “Configuration Menu 2” screen, press the F3 key to access the “Power” screen, as shown below:
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A
A U X
P O W E R
M O D U L E : N O
B
X F O R M E R
S I Z E :
1 2 0 V A C
C
B A T T E R Y
M A I N : Y
A U X : N
D
S U P E R V
A U X
P O W E R : Y E S
Exhibit 4-34: Power Screen (CyberCat 1016)
•
Row A - This field allows you to turn on/off supervision of the Supplemental Power Supply (SPS), if
installed (Yes/No). Use the
◄►
arrow keys to position the cursor under the field; then use the +/-
keys to toggle status.
•
Row B - This field allows you to select which AC power transformer is wired to the AC input terminal
(120/240VAC). Use the
◄►
arrow keys to position the cursor under the field; then use the +/- keys
to toggle status.
I
CAUTION
Selecting the incorrect transformer size could result in erratic
panel trouble conditions.
•
Row C - The BATTERY MAIN field allows you to turn on/off supervision of the Main controller
Battery Input terminals (Yes/No). Use the
◄►
arrow keys to position the cursor under the field;
then use the +/- keys to toggle status.
The AUX field allows you to turn on/off supervision of the Supplemental Power Supply Battery input
(
Yes/No
), if Supplemental Power Supply is installed. Use the
◄►
arrow keys to position the cursor
under the field; then use the
+/-
keys to toggle status.
L
Note:
Main or Auxiliary Supervision of battery selection of
NO
is not an allowed setting for UL.
•
Row D - This field allows you to turn on/off supervision of the 24 VDC Auxiliary Power circuits
(Yes/No). Use the
◄►
arrow keys to position the cursor under the field; then use the +/- keys to
toggle status.