4.0 CONFIGURATION MENU
CyberCat 254/1016 Programming Manual
4-47
P/N: 06-539
Rev 3, 08/2013
4.5.5.2 HOW TO SET THE FUNCTION OF THE PANEL’S ON-BOARD RELAYS
The Relay Functions screen lets you change the operating parameters of the CyberCat’s three on-board
relays and optional CRM4 relays if installed.
From the “Relay Configuration Menu” screen, press the F2 key to access the “Relay Functions” screen, as
shown below:
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A
R E L A Y
P 1 2 A :
D I S A B L E D
B
S T A T E :
A L A R M
C
S I L E N C E : N O
D R I L L : N O
D
R E S T A R T
D E L A Y : 0 0 0 S E C
Exhibit 4-73: Relay Functions Screen
•
Row A - This field allows you to select the relay to configure (P2 relays NUM1-3, P12A-D, P13A-D).
Use the
◄►
arrow keys to move the cursor under the field; then use the +/- keys to select a
different relay.
This field allows you to set the Enable/Disable status of the selected relay. Use the
◄►
arrow keys
to move the cursor under the field; then use the
+/-
keys to toggle the relay status.
L
Note:
The default state for Relay NUM3 is Trouble and it’s configuration parameters can not be
changed.
•
Row B - This field allows you to set the relay activation state (i.e., Alarm, Pre Alarm #2, Process,
Trouble, Supervisory, Zone Disable, Pre Alarm #1) for the relay selected in Row A. Use the
◄►
arrow keys to move the cursor under the field; then use the +/- keys to toggle the desired state.
•
Row C - This field allows you to set the Silenceable and Drill Enabled/Disabled (Y/N) status for the
relay selected in Row A. Use the
◄►
arrow keys to move the cursor under the field; then use the
+/- keys to toggle to the desired status.
•
Row D - This field allows you to set the CRM4 relay selected in Row A for fan restart operation by
assigning it a restart delay time (40 – 250 seconds). Use the
◄►
arrow keys to move the cursor
under the field; then use the +/- keys to toggle to the desired delay time. Once a delay time is
selected, the relay will become normally energized and will only de-energize upon activation of the
assigned state and zone. Once de-energized, the relay will not energize until after the panel has
been reset and the set time delay has expired. Fan restart relays will not change state through a
panel reset.
L
Note:
By default, the restart delay is set to ‘000’ allowing the relay to operate as a normally de-
energized relay with no restart delay.