10: confIGuratIon
Parame-
ter 21 No. 41 No. 52 No. 54 No. 151 No. 153 No. 63 No. 64
0 or 1
x
x
x
x
2 or 3
x
4 or 5
x
x
Available parameters:
20.
Input 1 - operating mode
This parameter allows to choose mode of 1st input (IN1). Change it
depending on connected device.
Parameter size
1B
Default value
2 (monostable button)
Available
values
0 – Normally closed alarm input (Notification)
1 – Normally open alarm input (Notification)
2 – Monostable button (Central Scene)
3 – Bistable button (Central Scene)
4 – Analog input without inter-
nal pull-up (Sensor Multilevel)
5 – Analog input with internal pull-
up (Sensor Multilevel)
21.
Input 2 - operating mode
This parameter allows to choose mode of 2nd input (IN2). Change
it depending on connected device.
Parameter size
1B
Default value
2 (monostable button)
Available
values
0 – Normally closed alarm
input (Notification CC)
1 – Normally open alarm input (Notification CC)
2 – Monostable button (Central Scene CC)
3 – Bistable button (Central Scene CC)
4 – Analog input without inter-
nal pull-up (Sensor Multilevel CC)
5 – Analog input with internal pull-
up (Sensor Multilevel CC)