Commissioning
© Festo Didactic • MPS
®
PA Compact Workstation
61
Symbol
PIN
assignment
EasyPort/
Simbox
address
PLC
address
Descritption
Binary inputs (XMA1)
B102
I 0
I 0
Flow rate sensor (frequence 0...1000Hz)
S111
I 1
I 1
Float switch, oveflow tank B101
S112
I 2
I 2
Float switch tank B102
B113
I 3
I 3
Capacitive sensor min. level tank B101
B114
I 4
I 4
Capacitive sensor max. level tank 101
S115
I 5
I 5
Micro switch 2-way ball valve V102 closed
S116
I 6
I 6
Micro switch 2-way ball valve V102 opened
-
I 7
I 7
Not used
Binary outputs (XMA1)
M102
O 0
Q 0
Open 2-way ball valve V102
E104
O 1
Q 1
Switch ON heating tank 101
K1
O 2
Q 2
Relay, select pump 0=binary/1=analogue
M1
O 3
Q 3
Switch ON pump P101 binary
M106
O 4
Q 4
Switch ON proportional valve V106
-
O 5
Q 5
Not used
-
O 6
Q 6
Not used
-
O 7
Q 7
Not used
Analogue inputs (X2)
LIC B101
UE1
AI 0
Process value PV, level in tank B102
FIC B102
UE2
AI 1
Process value PV, flow rate in pipe system
PIC B103
UE3
AI 2
Process value PV, pressure in pipe system
TIC B104
UE4
AI 3
Process value PV, temperature in tank B101
Analogue outputs (X2)
P101
UA1
AQ 0
Manipulated output CO, pump P101
V106
UA2
AQ 1
Manip. output CO, proportional valve V106
5.8
Allocation list of
inputs and outputs
Содержание MPS PA Compact
Страница 1: ...MPS PA Compact Workstation EN 12 08 Process automation MPS PA Compact Workstation Manual ...
Страница 10: ...Introduction 10 Festo Didactic MPS PA Compact Workstation ...
Страница 14: ...Technical data 14 Festo Didactic MPS PA Compact Workstation ...
Страница 16: ...Transport Unpacking Scope of delivery 16 Festo Didactic MPS PA Compact Workstation ...
Страница 68: ...Commissioning 68 Festo Didactic MPS PA Compact Workstation ...
Страница 70: ...Maintenance 70 Festo Didactic MPS PA Compact Workstation ...