Design and function
26
© Festo Didactic • MPS
®
PA Compact Workstation
The heating element is controlled by an internal micro controller,on activation of a
binary ouput (Q1 at XMA1).
Heating
Notes on safety:
•
The maximum operating temperature of the tanks must not 65 °C.
•
Do not operate the heating unit unless the heating element is fully immersed in
fluid.
•
Critical temperature at the heat element: at temperature around 50-60 °C the
heating is internal automatically switched off. If the temperature value drops
below 45 °C the heating is switched on again.
•
Critical temperature at the micro controller of the heating: at a semiconductor
temperature of around 90°C the heating is internal automatically switched off. If
the temperature value drops below 85 °C the heating is switched on again.
4.4
Heating