2. Import the device description file into the software
è
3. Configure the automation system CPX-AP in the software:
–
System structure
–
Network addressing
–
Address assignment of modules
è
Instruction manual for automation system CPX-AP
4. Transfer the automation project to the higher-order controller.
Behaviour of the display components of the module after error-free commissioning
[MD]
[SD]
[PL]
[MT]
Illuminated green
Illuminated green
Illuminated green
Off
Tab. 10 Behaviour of the display components after error-free commissioning
[LA X1], [LA X2]
[RUN]
[ERR]
Illuminated green
Illuminated green
Off
Tab. 11 Behaviour of the display components after error-free commissioning
Information on troubleshooting in the event of incorrect behaviour:
è
Instruction manual for automation system CPX-AP
è
10 Diagnostics and Fault Clearance
9
Parameterisation
Various parameters are available for reading out information about the modules in an automation sys-
tem CPX-AP and adapting the modules to the application situation.
Every configured or connected module also provides some of its parameters as network parameters.
These are then displayed in the objects 0x2000 … 0x2FFF.
ID
Parameter
Instance-
s
Data
type
Access
1)
Arraysize
246
Fieldbus serial number
1
UINT32
ro
–
791
Product key
1
CHAR
ro
12
960
Firmware version
1
CHAR
ro
40
20000
Module code
1
UINT32
ro
–
Parameterisation
11
Festo — CPX-AP-I-EC-M12 — 2019-11