ID
Parameter
Instance-
s
Data
type
Access
1)
Arraysize
20022
Configuration of voltage monitoring load
supply PL
–
0: load voltage monitoring inactive
–
1: load voltage monitoring active, with
suppression of diagnostics at switch-
off (factory setting)
–
2: load voltage monitoring active
1
UINT8
rw
–
20059
AP Sync operating mode
1
ENUM_ID ro
–
20085
Measured value temperature AP-ASIC [°C]
1
INT16
ro
–
20087
Current measured value of logic supply PS
[mV]
1
UINT16
ro
–
20088
Current measured value of load supply PL
[mV]
1
UINT16
ro
–
20092
Operating time [s]
1
UINT32
ro
–
20093
Hardware version
1
UINT8
ro
–
20196
Diagnostic status
–
Index 0: diagnostic status of the entire
automation system CPX-AP
–
Index 1: diagnostic status of module 1
(address 1)
–
Index 2: diagnostic status of module 2
(address 2)
–
...
Each entry is of the data type UINT8 with
the following meaning:
–
Bit 0: degree of severity information (1)
–
Bit 1: degree of severity maintenance
(1)
–
Bit 2: degree of severity warning (1)
–
Bit 3: degree of severity error (1)
–
Bit 4, 5: reserved
–
Bit 6: module present (1), module lost
(0)
–
Bit 7: reserved
Bit 6 is not valid for index 0.
1
UINT8
ro
Number
of mod-
ules + 1
1130125
Bootloader version
1
CHAR
ro
40
1) ro = read only; rw = read write
Tab. 12 Parameter
Parameterisation
12
Festo — CPX-AP-I-EC-M12 — 2019-11