ID hex (dec)
Message
Description
06
|
00
|
0189
(100663689)
Module identification
check failed
Diagnost-
ic status
Error
Transferred device address is invalid.
Remedy
–
Check address configuration. Is the con-
figuration set via software or hardware
(DIL switch)?
–
Check the assigned address for the
device.
–
Check multiple address assignment.
–
Check the DIL-switch setting.
08
|
00
|
012E
(134218030)
Device address
invalid
Diagnost-
ic status
Warning
Calculate bus cycle time failed (local timer too slow).
Remedy
–
Increase cycle time.
08
|
00
|
0192
(134218130)
Invalid cycle time
Diagnost-
ic status
Error
The communication to the AP Master is aborted.
Remedy
–
Restart AP Master.
–
Check communication cable (AP).
08
|
01
|
0124
(134283556)
AP Master lost
Diagnost-
ic status
Error
The AP system communication to a module is aborted.
Remedy
–
Restart AP system.
–
Check the cable.
08
|
01
|
0127
(134283559)
Communication to AP
module interrupted
Diagnost-
ic status
Error
Output process data Watchdog of the AP module expired.
Remedy
–
Match cycle time and watchdog paramet-
ers.
–
Restart AP system.
–
Check the cable.
08
|
01
|
0130
(134283568)
Output process data
Watchdog of the AP
module expired
Diagnost-
ic status
Error
Diagnostics and Fault Clearance