3. Diagnosis and error treatment
3-5
Festo P.BE-CPV-CO3-EN en 1201a
3.1.2
Fault diagnosis with the LEDs
Operating voltage for the electronics/sensors
(LED PS)
LED
Display
Operating status
Fault treatment
PS
off
The operating voltage for the
electronics/sensors is not applied
•
Check operating voltage supply
(pin 1)
PS
flashes
slowly
(green)
Operating voltage for the elec-
tronics/sensors in the CPV Direct or
in the extension string < 20.4 V
PS
flashes fast
(green)
The set CANopen address is not
permitted
•
Correct bus address
PS
lights up
green
The operating voltage for the
electronics and sensors is applied
–
Tab. 3/2:
Fault diagnosis with the green LED PS
Содержание CPV...-GE-CO3-8 series
Страница 2: ......
Страница 14: ...Contents and general instructions XII Festo P BE CPV CO3 EN en 1201a...
Страница 15: ...Installation 1 1 Festo P BE CPV CO3 EN en 1201a Chapter 1 Installation...
Страница 59: ...Commissioning 2 1 Festo P BE CPV CO3 EN en 1201a Chapter 2 Commissioning...
Страница 78: ...2 Commissioning 2 20 Festo P BE CPV CO3 EN en 1201a...
Страница 79: ...Diagnosis and error treatment 3 1 Festo P BE CPV CO3 EN en 1201a Chapter 3 Diagnosis and error treatment...
Страница 98: ...3 Diagnosis and error treatment 3 20 Festo P BE CPV CO3 EN en 1201a...
Страница 104: ...A Technical appendix and accessories A 6 Festo P BE CPV CO3 EN en 1201a A 3 Accessories www festo com catalogue...
Страница 105: ...Object directories B 1 Festo P BE CPV CO3 EN en 1201a Appendix B Object directories...
Страница 129: ...Examples C 1 Festo P BE CPV CO3 EN en 1201a Appendix C Examples...
Страница 136: ...C Examples C 8 Festo P BE CPV CO3 EN en 1201a...
Страница 137: ...Index D 1 Festo P BE CPV CO3 EN en 1201a Appendix D Index...
Страница 138: ...D Index D 2 Festo P BE CPV CO3 EN en 1201a Contents D Index D 1...