4.3
Activation via PROFIBUS
4.3.1
I/O card BasicIO (optional)
As an option, the BasicIO card can be omitted when activating via PROFIBUS. The BasicIO
card's signals are then transmitted via PROFIBUS.
BasicIO
Signal
Name
Function
Control
sovereignty
required
Description
DO:0
doutError
CMXR error active
No
DO:1
Reserved
--
DO:2
doutAutoSelected * Automatic operation mode set No
DO:3
doutManSelected * Manual operation mode set
No
DO:4
Unassigned
For free use
DO:5
Unassigned
For free use
DO:6
Unassigned
For free use
DO:7
Unassigned
For free use
DI:0
dinEMStop
Emergency stop
No
System manual
DI:1
dinEnabling
Permission button
No
System manual
DI:2
dinAutoSelect *
Automatic operation mode
No
DI:3
dinManSelect *
Manual operation mode
No
DI:4
Unassigned
For free use
DI:5
Unassigned
For free use
DI:6
Unassigned
For free use
DI:7
Unassigned
For free use
(*) The mode can also be selected via PROFIBUS as an option.